Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ACI CONST. CO., INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ACI CONST. CO., INC. in 539 SOUTH MAIN STREET, FINDLAY, OH 45840 (NAICS 236220). OSHA activity number 344444997.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ACI Const. CO., INC. — free Get an email when a new federal OSHA severe-injury report for ACI Const. CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
539 SOUTH MAIN STREET
City
FINDLAY
State
OH
ZIP
45840
Mailing
1700 FOSTORIA AVE. SUITE 800 P.O. BOX 390, FINDLAY, OH 45839
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236220
Employees
15
Ownership type
A

5 citations on file for this inspection.

1926.21 B02

Serious Gravity 10 1 instance 3 exposed
Issued
Dec 23, 2019
Penalty
Initial $9,282 · Current $9,282

Hazardous substances 8870

29 CFR 1926.21(b)(2): The employer did not instruct each employee in the recognition and avoidance of unsafe conditions and the regulations applicable to his work environment to control or eliminate any hazards or other exposure to illness or injury.  a. ACI Const. Co., Inc. jobsite located at 539 South Main Street, Findlay, OH:  On or about November 6, 2019 the employer did not ensure employees working on the third floor of the MPLX building were trained on the following information:          1. The requirement to test for induced voltage and backfeed voltage on circuits prior to exposing themselves to potentially energized conductors.      2. The requirement to test for voltages between 50 and 100 volts on potentially live conductors prior to performing work.
Recent events (1)
  • — Z (S) $9282

1926.416 A01

Serious Gravity 10 1 instance 3 exposed
Issued
Dec 23, 2019
Penalty
Initial $0 · Current $0
29 CFR 1926.416(a)(1): The employer permitted an employee to work in such proximity to any part of an electric power circuit that the employee could contact the electric power circuit in the course of work, unless the employee was protected against electric shock by deenergizing the circuit and grounding it or by guarding it effectively by insulation or other means.  a. ACI Const. Co., Inc. jobsite located at 539 South Main Street, Findlay, OH:  The employer did not ensure employees performing electrical work on the third floor of the MPLX building de-energized the lighting circuit prior to performing the work.  Employees de-energized the circuit prior to disconnecting the bank of lights but after the lights were disconnected from the main feed, they re-energized the circuit.  On November 6, 2019 an employee was attaching the wires from a recently installed bank of lights to the energized feed wires inside of a junction box and suffered a severe electric shock.
Recent events (1)
  • — Z (S) $0

1926.416 A03

Serious Gravity 10 1 instance 3 exposed
Issued
Dec 23, 2019
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1926.416(a)(3): Before work is begun the employer did not ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, is so located that the performance of the work may bring any person, tool, or machine into physical or electrical contact with the electric power circuit. The employer shall post and maintain proper warning signs where such a circuit exists. The employer shall advise employees of the location of such lines, the hazards involved, and the protective measures to be taken.  a. ACI Const. Co., Inc. jobsite located at 539 South Main Street, Findlay, OH:  On or about November 6, 2019 the employer did not ensure employees performing electrical work on the third floor of the MPLX building were properly testing de-energized circuits to determine inadvertent induced voltage, back feed voltage, or voltage between 50 and 100 volts was present.  The employees were using Fluke voltage detection pens to determine if voltage was present and the pens were not rated below 100 volts.
Recent events (1)
  • — Z (S) $0

1926.417 A

Serious Gravity 5 1 instance 3 exposed
Issued
Dec 23, 2019
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1926.417(a): Controls that are to be deactivated during the course of work on energized or deenergized equipment or circuits were not tagged.  a. ACI Const. Co., Inc. jobsite located at 539 South Main Street, Findlay, OH:  On or about November 6, 2019 the employer did not ensure employees moving lighting fixtures on the third floor of the MPLX building placed a lock or tag on the #4 breaker after de-energizing the electrical circuit to unwire the bank of lights.
Recent events (1)
  • — Z (S) $0

1926.97 C02 VIII

Other-than-serious 1 instance 3 exposed
Issued
Dec 23, 2019
Penalty
Initial $0 · Current $0

Hazardous substances 8870

29 CFR 1926.97(c)(2)(viii): Electrical protective equipment was not subjected to periodic electrical tests. Test voltages and the maximum intervals between tests shall be in accordance with Table E-4 and Table E-5.  a. ACI Const. Co., Inc. jobsite located at 539 South Main Street, Findlay, OH:  On or about November 13, 2019 the employer did not ensure insulted gloves used for protecting against electrical shock, were tested every 6 months.  The gloves located in the maintenance department, available for employees to use were last tested in January 2015.
Recent events (1)
  • — Z (O) $0

View ACI Const. CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344444997.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.