OSHA Inspection: R. KOHLMAN DEVELOPMENT, LLC

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of R. KOHLMAN DEVELOPMENT, LLC in 350 TECHNOLOGY DRIVE, PITTSBURGH, PA 15219 (NAICS 238210). OSHA activity number 344560768.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch R. Kohlman Development, LLC — free Get an email when a new federal OSHA severe-injury report for R. Kohlman Development, LLC is published. One employer, no account, unsubscribe in one click.
Site address
350 TECHNOLOGY DRIVE
City
PITTSBURGH
State
PA
ZIP
15219
Mailing
8024 BREN DINA COURT, MURRYSVILLE, PA 15668
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.403 B01

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 6, 2020
Penalty
Initial $5,398 · Current $4,398 Reduced
29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees.  Safety of equipment was not determined on the basis of arcing effects:    (a)  Jobsite, Electrical Room:  On or about January 14, 2020, the electrical contractor did not ensure that a #6 ground wire was not able to come in contact with energized electrical parts on the inside of the Main Distribution Panel (MDP).
Recent events (3)
  • — F (S) $4398
  • — C (S) $5398
  • — Z (S) $5398

1926.404 F08 II

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Apr 6, 2020
Penalty
Initial $0 · Current $0
29 CFR 1926.404(f)(8)(ii): Conductor used for grounding fixed or movable equipment did not have capacity to conduct safely any fault current which may be imposed on it:   (a)  Jobsite, Electrical Room:  On or about January 14, 2020, the #6 ground wire did not have the capacity to safely conduct any fault current which was imposed on it.  The #6 copper ground wire melted when it came in contact with the energized bus bar.