FORT WORTH, TX —
OSHA Inspection: MOAH ELECTRIC, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of MOAH ELECTRIC, INC. in 100 THROCKMORTON, FORT WORTH, TX 76102 (NAICS 238210). OSHA activity number 344562665.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- MOAH ELECTRIC, INC.
- Site address
- 100 THROCKMORTON
- City
- FORT WORTH
- State
- TX
- ZIP
- 76102
- Mailing
- 1602 STEVENS ST., DALLAS, TX 75228
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 35
- Ownership type
- A
Citations
6 citations on file for this inspection.
1910.333 A01
- Issued
- Apr 8, 2020
- Abate by
- May 6, 2020
- Penalty
- Initial $9,446 · Current $5,668 Reduced
General-duty citation text
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or near them. On or about January 11, 2020 and at times prior thereto, the employer did not ensure all electrical equipment circuits were deenergized prior to employees working on or near the live or energized equipment. Employees were exposed to electric shock and arc-flash hazards.
Recent events (2)
- — I (S) $5667.6
- — Z (S) $9446
1910.333 B02
- Issued
- Apr 8, 2020
- Abate by
- May 6, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2): The employer did not ensure all electrical equipment circuits were deenergized with a lock, a tag or both prior to employees working on or near the live or energized equipment. Employees were exposed to electric shock and arc-flash hazards: On or about January 10, 2020, and at times prior thereto, employees worked on a switch gear and relied on another company, Oncor Delivery, to deenergize or apply lockout/tagout devices which did not ensure employees were protected from all energized parts, and On or about January 11, 2020, and at times prior thereto, the employer did not ensure employees deenergized the equipment prior to opening a switch gear cabinet which exposed employees to an arch flash incident, and On or about January 11, 2020, and at times prior thereto, the employer did not ensure employees deenergized the equipment when a crew responded after an arch flash incident to finish repairing the switch gear.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.333 C02
- Issued
- Apr 8, 2020
- Abate by
- May 6, 2020
- Penalty
- Initial $9,446 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools On or about January 11, 2020, and at times prior thereto, the employer did not ensure employees who worked on a 480 volt switch gear was familiar with special precautionary techniques to work on particular switch gear equipment located in the mechanical room.
Recent events (2)
- — I (S) $0
- — Z (S) $9446
1910.335 A01 I
- Issued
- Apr 8, 2020
- Abate by
- Apr 29, 2020
- Penalty
- Initial $0 · Current $2,000
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. On or about January 11, 2020 and at times prior thereto, and at times thereafter, the employer did not ensure employees were provided and wore electrical personal protective equipment when opening an energized 480 volt electrical switch gear cabinet, exposing employees to arc flash hazards. Note: Personal protective equipment requirements are contained in subpart I of this part.
Recent events (2)
- — I (S) $2000
- — Z (S) $0
1910.137 C02 VIII
- Issued
- Apr 8, 2020
- Abate by
- May 6, 2020
- Penalty
- Initial $4,048 · Current $2,429 Reduced
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not periodically electrical tested. Test voltages and the maximum intervals between tests will be in accordance with Table I-4 and Table I-5. On or about January 10, 2020, and at times prior thereto, the employer did not ensure that insulated electrical rubber gloves were tested every six months.
Recent events (2)
- — I (S) $2428.8
- — Z (S) $4048
1910.132 D01
- Issued
- Apr 8, 2020
- Abate by
- May 6, 2020
- Penalty
- Initial $4,048 · Current $0 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): On or about January 10, 2020 and at times prior thereto, the employer did not assess the work place to determine if hazards were present and to determine the necessary PPE needed for safe work practices.
Recent events (2)
- — I (S) $0
- — Z (S) $4048
More inspections at Moah Electric, INC.
View Moah Electric, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344562665.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.