Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MOAH ELECTRIC, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of MOAH ELECTRIC, INC. in 100 THROCKMORTON, FORT WORTH, TX 76102 (NAICS 238210). OSHA activity number 344562665.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Moah Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Moah Electric, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
MOAH ELECTRIC, INC.
Site address
100 THROCKMORTON
City
FORT WORTH
State
TX
ZIP
76102
Mailing
1602 STEVENS ST., DALLAS, TX 75228
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
35
Ownership type
A

6 citations on file for this inspection.

1910.333 A01

Serious Gravity 10 1 instance 6 exposed
Issued
Apr 8, 2020
Abate by
May 6, 2020
Penalty
Initial $9,446 · Current $5,668 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee worked on or near them.    On or about January 11, 2020 and at times prior thereto, the employer did not ensure all electrical equipment circuits were deenergized prior to employees working on or near the live or energized equipment.  Employees were exposed to electric shock and arc-flash hazards.
Recent events (2)
  • — I (S) $5667.6
  • — Z (S) $9446

1910.333 B02

Serious Gravity 10 2 instances 6 exposed
Issued
Apr 8, 2020
Abate by
May 6, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2): While an employee was exposed to contact with parts of fixed electric equipment or circuits which were deenergized, the circuits energizing the parts were not locked out or tagged or both in accordance with the requirements of this paragraph (b) of 29 CFR 1910.333(b)(2):   The employer did not ensure all electrical equipment circuits were deenergized with a lock, a tag or both prior to employees working on or near the live or energized equipment.  Employees were exposed to electric shock and arc-flash hazards:   On or about January 10, 2020, and at times prior thereto, employees worked on a switch gear and relied on another company, Oncor Delivery, to deenergize or apply lockout/tagout devices which did not ensure employees were protected from all energized parts, and   On or about January 11, 2020, and at times prior thereto, the employer did not ensure employees deenergized the equipment prior to opening a switch gear cabinet which exposed employees to an arch flash incident, and  On or about January 11, 2020, and at times prior thereto, the employer did not ensure employees deenergized the equipment when a crew responded after an arch flash incident to finish repairing the switch gear.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 C02

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 8, 2020
Abate by
May 6, 2020
Penalty
Initial $9,446 · Current $0 Reduced
29 CFR 1910.333(c)(2): The employer did not ensure that only qualified persons were working on energized circuits and that qualified persons were familiar with the proper use of special precautionary techniques, personal protective equipment, insulating and shielding materials, and insulated tools      On or about January 11, 2020, and at times prior thereto, the employer did not ensure employees who worked on a 480 volt switch gear was familiar with special precautionary techniques to work on particular switch gear equipment located in the mechanical room.
Recent events (2)
  • — I (S) $0
  • — Z (S) $9446

1910.335 A01 I

Serious Gravity 10 1 instance 2 exposed
Issued
Apr 8, 2020
Abate by
Apr 29, 2020
Penalty
Initial $0 · Current $2,000
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed.       On or about January 11, 2020 and at times prior thereto, and at times thereafter, the employer did not ensure employees were provided and wore electrical personal protective equipment when opening an energized 480 volt electrical switch gear cabinet, exposing employees to arc flash hazards.      Note: Personal protective equipment requirements are contained in subpart I of this part.
Recent events (2)
  • — I (S) $2000
  • — Z (S) $0

1910.137 C02 VIII

Serious Gravity 1 1 instance 4 exposed
Issued
Apr 8, 2020
Abate by
May 6, 2020
Penalty
Initial $4,048 · Current $2,429 Reduced
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not periodically electrical tested. Test voltages and the maximum intervals between tests will be in accordance with Table I-4 and Table I-5.    On or about January 10, 2020, and at times prior thereto, the employer did not ensure that insulated electrical rubber gloves were tested every six months.
Recent events (2)
  • — I (S) $2428.8
  • — Z (S) $4048

1910.132 D01

Serious Gravity 1 1 instance 6 exposed
Issued
Apr 8, 2020
Abate by
May 6, 2020
Penalty
Initial $4,048 · Current $0 Reduced
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE):    On or about January 10, 2020 and at times prior thereto, the employer did not assess the work place to determine if hazards were present and to determine the necessary PPE needed for safe work practices.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4048

View Moah Electric, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344562665.