Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ENGLER ELECTRIC, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of ENGLER ELECTRIC, INC. in GRAND REHABILITATION AND NURSING OF UTICA 1657 SUNSET AVENUE, UTICA, NY 13502 (NAICS 238210). OSHA activity number 344571948.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Engler Electric, INC. — free Get an email when a new federal OSHA severe-injury report for Engler Electric, INC. is published. One employer, no account, unsubscribe in one click.
Site address
GRAND REHABILITATION AND NURSING OF UTICA 1657 SUNSET AVENUE
City
UTICA
State
NY
ZIP
13502
Mailing
609 COLOMBIA STREET, UTICA, NY 13502
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
50
Ownership type
A

4 citations on file for this inspection.

1910.132 D01 I

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Apr 22, 2020
Abate by
Apr 29, 2020
Penalty
Initial $10,390 · Current $8,000 Reduced
29 CFR 1910.132(d)(1)(i): The employer did not select and have each affected employee use, the types of personal protective equipment that would protect the affected employee(s) from the hazards identified in the hazard assessment:  a)  At the jobsite, on or about 1/3/20:  An electrician was replacing a panel on an energized 800 amp service cabinet where the face shield he was using was inappropriate for the work being performed, causing the worker to lift the shield to see the work at hand just prior to the arc-flash.
Recent events (3)
  • — J (O) $8000
  • — C (S) $10390
  • — Z (S) $10390

1910.132 D02

Deleted Serious Gravity 10 2 instances 2 exposed
Issued
Apr 22, 2020
Abate by
Apr 29, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.132(d)(2): The employer did not verify, through a written certification, that the required workplace hazard assessment had been performed:  a)  At the jobsite, on or about 1/3/20:  An electrician was working on an energized 800 amp service cabinet where a written hazard assessment was not performed.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.137 C02 VII C

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 22, 2020
Abate by
Apr 29, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.137(c)(2)(vii)(C): Any other class of glove may be used without protector gloves, under limited-use conditions, when small equipment and parts manipulation necessitate unusually high finger dexterity but only if the employer can demonstrate that the possibility of physical damage to the gloves is small and if the class of glove is one class higher than that required for the voltage involved.  b)  At the jobsite, on or about 1/3/20:  An electrician was replacing a panel on an energized 800 amp service cabinet where the gloves he was using were too thick to manipulate the attachment screws, causing the worker to remove one glove to handle the screw and leaving that hand unprotected just prior to the arc-flash.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.333 A01

Repeat Gravity 10 1 instance 2 exposed
Issued
Apr 22, 2020
Abate by
Apr 29, 2020
Penalty
Initial $20,781 · Current $13,000 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before the employee works on or near them.  a)  At the jobsite, on or about 1/3/20:  An electrician was working on an energized 800 amp service cabinet.  And following the arc-blast a generator was provided to supply power to non life-critical services in the building.    Engler Electric was previously cited for a violation of this occupational safety and health standard or its equivalent standard (CFR 1910.333(a)(1), which was contained in OSHA inspection number 11221188, citation number 1, item number 2, and was affirmed as a final order on 5/27/16, with respect to a workplace located at    200 South Washington Street, Herkimer, NY.
Recent events (3)
  • — J (R) $13000
  • — C (R) $20781
  • — Z (R) $20781

View Engler Electric, INC.'s full OSHA safety record →