On , OSHA opened a planned safety inspection of ABC SUPPLY CO., INC. in 2035 E 66TH AVE., DENVER, CO 80229 (NAICS 423330). OSHA activity number 344579321.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ABC SUPPLY CO., INC.
- Site address
- 2035 E 66TH AVE.
- City
- DENVER
- State
- CO
- ZIP
- 80229
- Mailing
- 2035 E 66TH AVE., DENVER, CO 80229
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 423330
- Employees
- 41
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1910.303 B08 I
- Issued
- Jan 31, 2020
- Abate by
- Feb 27, 2020
- Penalty
- Initial $4,916 · Current $3,400 Reduced
General-duty citation text
29 CFR 1910.303(b)(8)(i): Electrical equipment was not firmly secured to the surface on which it was mounted: (a) ABC Supply Co, Inc. at 2035 E. 66th Ave. Denver, CO 80229: On or before 1/24/2020 the employer did not ensure that electrical equipment including steel conduit and outlet boxes were securely placed. Metal conduit and an outlet box were found suspended, supported only by the electrical cord enclosed within the conduit. This condition exposed employees to electrical shock and fire hazards.
Recent events (2)
- · I (S) $3400
- · Z (S) $4916
1910.303 G01 I
- Issued
- Jan 31, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1: (a) ABC Supply Co, Inc. at 2035 E. 66th Ave. Denver, CO 80229: On or before 1/24/2020 the employer did not ensure that items were stored at least 30 inches away from the faces of the electrical panels in the warehouse. A space heater and a cardboard box were stored within 30 inches of the electrical panels. This condition exposed employees to electric shock and fire hazards.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 A02 I
- Issued
- Jan 31, 2020
- Abate by
- Feb 27, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners: Note: Temporary electrical power and lighting installation(s) may only be used as specified by 1910.305(a)(2)(i)(A) through 1910.305(a)(2)(i)(C): (a) ABC Supply Co, Inc. at 2035 E. 66th Ave. Denver, CO 80229: On or before 1/24/2020 the employer did not ensure that a pump used for a Diesel Exhaust Fluid (DEF) tote was powered in accordance with this standard. An extension cord was used in lieu of permanent wiring for the purpose of powering the DEF pump. This condition exposed employees to electric shock and fire hazards.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections at ABC Supply CO., INC.
View ABC Supply CO., INC.'s full OSHA safety record →
More inspections in this industry (NAICS 423330)
More inspections in CO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 344579321.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.