CLINTON, NY ·
OSHA Inspection: CALKINS DRYWALL, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CALKINS DRYWALL, INC. in LEWISTON AT SENECA, 7856 STATE ROUTE 5, CLINTON, NY 13323 (NAICS 238310). OSHA activity number 344593397.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CALKINS DRYWALL, INC.
- Site address
- LEWISTON AT SENECA, 7856 STATE ROUTE 5
- City
- CLINTON
- State
- NY
- ZIP
- 13323
- Mailing
- 8848 SOUTH SENECA STREET, WEEDSPORT, NY 13166
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238310
- Employees
- 15
- Ownership type
- Private (A)
Citations
3 citations on file for this inspection.
1926.403 B02
- Issued
- May 1, 2020
- Penalty
- Initial $3,084 · Current $1,850 Reduced
General-duty citation text
29 CFR 1926.403(b)(2): Listed, labeled, or certified equipment was not installed and used in accordance with instructions included in the listing, labeling, or certification: a) Building #1, Unit #2, first floor, on or about 1-30-20: Two employees were operating a hand held electric drill that was plugged into a relocatable power tap (RPT) that was not being used in accordance with the manufacturers recommendations or as listed and labeled.
Recent events (2)
- · I (S) $1850.4
- · Z (S) $3084
1926.404 B01 II
- Issued
- May 1, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection: a) Building #1, Unit #2, first floor, on or about 1-30-20: Two employees were operating a hand held electric drill that was powered through an extension cord that did not have a continuous path to ground due to missing ground pin.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1926.405 G02 IV
- Issued
- May 1, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.405(g)(2)(iv): Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws: a) Building #1, Unit #2, first floor, on or about 1-30-20: Two employees were operating a hand held electric drill, equipped with a power cord that exhibited a broken strain relief.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections at Calkins Drywall, INC.
View Calkins Drywall, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238310)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 344593397.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.