On , OSHA opened a planned safety inspection of ESSEX HOMES OF WNY, INC in 650 N ELLICOTT CREEK ROAD, AMHERST, NY 14228 (NAICS 236116). OSHA activity number 344631726.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Essex Homes of WNY, INC — free Get an email when a new federal OSHA severe-injury report for Essex Homes of WNY, INC is published. One employer, no account, unsubscribe in one click.
Site address
650 N ELLICOTT CREEK ROAD
City
AMHERST
State
NY
ZIP
14228
Mailing
8940 MAIN STREET, CLARENCE, NY 14031
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
236116
Employees
2
Ownership type
A

2 citations on file for this inspection.

1926.153 K02

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 18, 2020
Penalty
Initial $1,671 · Current $1,025 Reduced
29 CFR 1926.153(k)(1): LP-Gas containers were not stored outside of buildings in accordance with the distances shown on Table F-3:  a) On or about 2/11/20, at the site of Amherst, NY. Four 500-pound propane tanks were stored outside of buildings and were 5 feet away from the buildings, not in accordance with 10 feet distance shown on Table F-3.   NO ABATEMENT CERTIFICATION REQUIRED
Recent events (2)
  • — I (S) $1025
  • — Z (S) $1671

1926.153 L

Serious Gravity 1 1 instance 1 exposed
Issued
Feb 18, 2020
Penalty
Initial $1,671 · Current $1,025 Reduced
29 CFR 1926.153(l): LP-Gas storage locations were not provided with at least one approved portable fire extinguisher having a rating of not less than 20B:C:  a) On or about 2/11/20, at the site of Amherst, NY. Four 500-pound propane tanks were stored outside of buildings and the storage location lacked at least one approved portable fire extinguisher.