Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: LAKE SHORE BURIAL VAULT CO., INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of LAKE SHORE BURIAL VAULT CO., INC. in 12780 WEST LISBON ROAD, BROOKFIELD, WI 53005 (NAICS 327390). OSHA activity number 344652839.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Lake Shore Burial Vault CO., INC. — free Get an email when a new federal OSHA severe-injury report for Lake Shore Burial Vault CO., INC. is published. One employer, no account, unsubscribe in one click.
Site address
12780 WEST LISBON ROAD
City
BROOKFIELD
State
WI
ZIP
53005
Mailing
12780 WEST LISBON ROAD, BROOKFIELD, WI 53005
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
327390
Employees
26
Ownership type
A

2 citations on file for this inspection.

1910.303 G01 I B

Other-than-serious 1 instance 6 exposed
Issued
May 29, 2020
Abate by
Jun 17, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1)(i)(B): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the width of the working space in front of electrical equipment was less than the width of the equipment or 762 mm (30 inches), whichever was greater :    (a)  On or about February 25, 2020, in the northeast corner of the Pour Room, the working space around, and in front the two Electric Breaker Switch boxes was being used for the storage of hand tools, assorted sheet metal pieces and wheel barrow(s). This condition did not allow sufficient entrance, and access to the two 120/240 volt electrical panels/disconnects.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.303 E01 II

Other-than-serious 1 instance 10 exposed
Issued
May 29, 2020
Abate by
Jun 17, 2020
Penalty
Initial $3,441 · Current $0 Reduced
29 CFR 1910.303(e)(1)(ii): Electrical equipment were not marked giving voltage, current, wattage or other ratings as necessary:    (a) On or about February 25, 2020, in the northeast corner of the Pour Room, electrical panels that were being used to supply 120/240 volt power to facility equipment were not properly marked to alert employee(s) as to the associated voltage in use, and the related hazards. This exposed employee(s) to potential electric shock and arc flash hazard.
Recent events (2)
  • — I (O) $0
  • — Z (S) $3441

View Lake Shore Burial Vault CO., INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344652839.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.