Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: US DEPT OF AGRICULTURE

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of US DEPT OF AGRICULTURE in 1809 SUITE C, ASSOCIATES LANE, CHARLOTTE, NC 28217 (NAICS 926140). OSHA activity number 344697180.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch US Dept of Agriculture — free Get an email when a new federal OSHA severe-injury report for US Dept of Agriculture is published. One employer, no account, unsubscribe in one click.
Site address
1809 SUITE C, ASSOCIATES LANE
City
CHARLOTTE
State
NC
ZIP
28217
Mailing
1809 SUITE C, ASSOCIATES LANE, CHARLOTTE, NC 28217
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
926140
Employees
3
Ownership type
D

2 citations on file for this inspection.

1910.303 B02

Serious Gravity 5 2 instances 3 exposed
Issued
Apr 2, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:      Storage Area:  On or about March 10, 2020 , a Fellowes relocatable power tap, designed and listed for being used with high concentrations of low powered loads was instead used with high powered loads such as a two deep freezers.   CORRECTED DURING INSPECTION
Recent events (1)
  • — Z (S) $0

1910.303 G01

Serious Gravity 1 1 instance 1 exposed
Issued
Apr 2, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(g)(1): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  Storage Room:  On or about 03/10/2020, the employer did not ensure sufficient working space of at least 3ft. for a wall mounted 240 volt electrical panel whereby a file cabinet and traffic cone were placed in front of the panel.     CORRECTED DURING INSPECTION
Recent events (1)
  • — Z (S) $0

View US Dept of Agriculture's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344697180.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.