OSHA Inspection: S & V EXXON, LLC

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of S & V EXXON, LLC in 111 MARSHALL ST, BENWOOD, WV 26031 (NAICS 811111). OSHA activity number 344700232.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch S & V Exxon, LLC — free Get an email when a new federal OSHA severe-injury report for S & V Exxon, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
S & V EXXON, LLC
Site address
111 MARSHALL ST
City
BENWOOD
State
WV
ZIP
26031
Mailing
111 MARSHALL ST, BENWOOD, WV 26031
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811111
Employees
6
Ownership type
A

10 citations on file for this inspection.

1910.37 A03

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.37(a)(3): Exit route(s) were not kept free and unobstructed:  (a) Repair shop - On or about 3/16/2020, an exit door was obstructed by tools and materials placed in front of the exit door, exposing employees to fire hazards.
Recent events (1)
  • — Z (S) $0

1910.37 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "Exit":  (a) Repair shop - On or about 3/16/2020, exit doors were not marked, exposing employees to fire hazards.
Recent events (1)
  • — Z (S) $0

1910.141 D02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.141(d)(2)(ii): Lavatories were not provided with hot and cold, or tepid running water:  (a) Restroom - On or about 3/16/2020, the lavatory was not provided with hot or tepid running water, exposing employees to chemical and biological hazards.
Recent events (1)
  • — Z (S) $0

1910.212 A05

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.212(a)(5): Fan blade guard(s) were not provided where the periphery of the blades was less than seven feet from the floor or working level:  (a) Oil change bay - On or about 3/16/2020, a fan on an air compressor was not guarded, exposing employees to caught-in and amputation hazards.
Recent events (1)
  • — Z (S) $0

1910.219 D01

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.219(d)(1): Pulley(s) with part(s) seven feet or less from the floor or work platform were not guarded in accordance with the requirements specified in 29 CFR 1910.219(m) and (o):  (a) Oil change bay - On or about 3/16/2020, the motor and compressor pulleys on an air compressor were not guarded, exposing employees to caught-in and amputation hazards.
Recent events (1)
  • — Z (S) $0

1910.219 E03 I

Serious Gravity 10 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.219(e)(3)(i): Vertical or inclined belt(s) were not enclosed by guard(s) conforming to the requirements specified at 29 CFR 1910.219(m) and (o):  (a) Oil change bay - On or about 3/16/2020, the v-belts driving the compressor pulleys on an air compressor were not guarded, exposing employees to caught-in and amputation hazards.
Recent events (1)
  • — Z (S) $0

1910.215 A04

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.215(a)(4): Work rest(s) on grinding machinery were not adjusted closely to the wheel with a maximum opening of one eighth inch:  (a) Tire/Inspection shop - On or about 3/16/2020, the employer allowed employees to operate a bench grinder with a work rest which was 1/2 of an inch from the grinding surface, exposing employees to caught-in, struck-by, and amputation hazards.
Recent events (1)
  • — Z (S) $0

1910.215 B09

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.215(b)(9): The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:  (a) Tire/Inspection shop - On or about 3/16/2020, the employer allowed employees to operate a bench grinder with a tongue guard which was 3/4 of an inch from the grinding surface, exposing employees to caught-in, struck-by, and amputation hazards.
Recent events (1)
  • — Z (S) $0

1910.303 B07 I

Serious Gravity 5 3 instances 6 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment  (a) Tire/Inspection shop - On or about 3/16/2020, a 240 volt breaker panel had unused opening which were not closed, exposing employees to electrical shock and fire hazards.  (b) Repair shop - On or about 3/16/2020, a 110 volt duplex outlet box had unused openings which were not closed, exposing employees to electrical shock and fire hazards.  (c) Tire/Inspection shop - On or about 3/16/202, a 240 volt breaker subpanel had unused openings which were not closed, exposing employees to electrical shock and fire hazards.
Recent events (1)
  • — Z (S) $0

1910.304 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 24, 2020
Abate by
Sep 1, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.304(a)(2): Grounded conductors were attached to terminals or leads so as to reverse designated polarity:  (a) Repair shop - On or about 3/16/2020, a 110 volt duplex outlet box connected in a manner which reversed it's designated polarity, exposing employees to electrical shock hazards.