OSHA Inspection: PIKE ELECTRIC, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of PIKE ELECTRIC, LLC in 2609 14TH ST., GULFPORT, MS 39501 (NAICS 237130). OSHA activity number 344725692.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Pike Electric, LLC for free Get an email when a new federal OSHA severe-injury report for Pike Electric, LLC is published. One employer, no account, unsubscribe in one click.
Establishment
PIKE ELECTRIC, LLC
Site address
2609 14TH ST.
City
GULFPORT
State
MS
ZIP
39501
Mailing
100 PIKE WAY, MOUNT AIRY, NC 27030
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
1589
Ownership type
Private (A)

2 citations on file for this inspection.

1926.961 C02

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jun 23, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1926.961(c)(2): The employer did not ensure that all switches, disconnectors, jumpers, taps, and other means through which known sources of electric energy may be supplied to the particular lines and equipment to be de-energized were open.  The employer did not render such means inoperable and then ensure that such means were tagged to indicate that employees were at work.  (a) 2609 14th St. Gulfport, MS. - On or about April 14, 2020 The employer did not ensure that the electrical circuit # 225743 was deenergized exposing employees to electrocution hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $13494

1926.960 G05 IV

Deleted Repeat 1 instance 2 exposed
Issued
Jun 23, 2020
Abate by
Jul 17, 2020
Penalty
Initial $10,604 · Current $0 Reduced
29 CFR 1926.960(g)(5)(iv): The protection for the employee's head may consist of head protection meeting � 1926.100(b)(2) and a faceshield with a minimum arc rating of 8 cal/cm2 if the estimated incident energy exposure is less than 13 cal/cm2 for exposures involving single-phase arcs in open air or 9 cal/cm2 for other exposures, and  (a) 2609 14th St. Gulfport, MS. alley - On or about April 14, 2020 the employer did not provide adequate face protection (faceshield) for employees while working on energized electrical line exposing them to ark flash hazards.  Pike Electric, LLC was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1926.960(g)(5)(iv), which was contained in OSHA inspection number 1421433, citation number 1, item number 3 and was affirmed as a final order on 12/18/2019, with respect to a workplace located at 226 Schrock Rd. Garrett, PA.
Recent events (2)
  • · I (R) $0
  • · Z (R) $10604

View Pike Electric, LLC's full OSHA safety record →