AUSTIN, TX ·
OSHA Inspection: NAVEJAS ELECTRIC, LLC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of NAVEJAS ELECTRIC, LLC. in 400 E. ANDERSON LOOP, AUSTIN, TX 78753 (NAICS 238210). OSHA activity number 344740287.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- NAVEJAS ELECTRIC, LLC.
- Site address
- 400 E. ANDERSON LOOP
- City
- AUSTIN
- State
- TX
- ZIP
- 78753
- Mailing
- 902 OLD AUSTIN HUTTO RD,, PFLUGERVILLE, TX 78660
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Union (A)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 37
- Ownership type
- Private (A)
Citations
2 citations on file for this inspection.
1926.416 A03
- Issued
- Oct 29, 2020
- Abate by
- Nov 4, 2020
- Penalty
- Initial $9,446 · Current $6,446 Reduced
General-duty citation text
29 CFR 1926.416(a)(3): Before work was begun the employer did not ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit; the employer did not post and maintain proper warning signs where such a circuit existed; and the employer did not advise employees of the location of such lines, the hazards involved, and the protective measures to be taken: On or about May 1, 2020, employees were conducting electrical demolition operations on the load side of the fifth floor electrical disconnect in the building being remodeled while it was energized, exposing employees to the hazard of being electrocuted, shocked or burned.
Recent events (3)
- · F (S) $6446
- · C (S) $9446
- · Z (S) $9446
1926.416 D
- Issued
- Oct 29, 2020
- Abate by
- Nov 4, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.416(d): Special tools insulated for the voltage were not used while installing or removing fuses with one or both terminals energized: On or about May 1, 2020, an employee removed the fuses from a 480V energized service disconnect during electrical demolition operations on the fifth floor of the building being remodeled without utilizing insulated tools, exposing the employee to the hazard of being electrocuted, shocked or burned.