OSHA Inspection: NAVEJAS ELECTRIC, LLC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NAVEJAS ELECTRIC, LLC. in 400 E. ANDERSON LOOP, AUSTIN, TX 78753 (NAICS 238210). OSHA activity number 344740287.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Navejas Electric, LLC. for free Get an email when a new federal OSHA severe-injury report for Navejas Electric, LLC. is published. One employer, no account, unsubscribe in one click.
Site address
400 E. ANDERSON LOOP
City
AUSTIN
State
TX
ZIP
78753
Mailing
902 OLD AUSTIN HUTTO RD,, PFLUGERVILLE, TX 78660
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Union (A)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
37
Ownership type
Private (A)

2 citations on file for this inspection.

1926.416 A03

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 29, 2020
Abate by
Nov 4, 2020
Penalty
Initial $9,446 · Current $6,446 Reduced
29 CFR 1926.416(a)(3): Before work was begun the employer did not ascertain by inquiry or direct observation, or by instruments, whether any part of an energized electric power circuit, exposed or concealed, was so located that the performance of the work could bring any person, tool, or machine into physical or electrical contact with the electric power circuit; the employer did not post and maintain proper warning signs where such a circuit existed; and the employer did not advise employees of the location of such lines, the hazards involved, and the protective measures to be taken:  On or about May 1, 2020, employees were conducting electrical demolition operations on the load side of the fifth floor electrical disconnect in the building being remodeled while it was energized, exposing employees to the hazard of being electrocuted, shocked or burned.
Recent events (3)
  • · F (S) $6446
  • · C (S) $9446
  • · Z (S) $9446

1926.416 D

Deleted Serious Gravity 5 1 instance 3 exposed
Issued
Oct 29, 2020
Abate by
Nov 4, 2020
Penalty
Initial $0 · Current $0
29 CFR 1926.416(d): Special tools insulated for the voltage were not used while installing or removing fuses with one or both terminals energized:  On or about May 1, 2020, an employee removed the fuses from a 480V energized service disconnect during electrical demolition operations on the fifth floor of the building being remodeled without utilizing insulated tools, exposing the employee to the hazard of being electrocuted, shocked or burned.
Recent events (3)
  • · F (S) $0
  • · C (S) $0
  • · Z (S) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 344740287.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.