WAUWATOSA, WI —
OSHA Inspection: THE LUTHERAN HOME, INC.
Referral inspection · Health discipline
At a glance
On , OSHA opened a referral health inspection of THE LUTHERAN HOME, INC. in 7500 W NORTH AVE., WAUWATOSA, WI 53213 (NAICS 623110). OSHA activity number 344782917.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE LUTHERAN HOME, INC.
- Site address
- 7500 W NORTH AVE.
- City
- WAUWATOSA
- State
- WI
- ZIP
- 53213
- Mailing
- 7500 W NORTH AVE, WAUWATOSA, WI 53213
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Health
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623110
- Employees
- 425
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.147 C06 I
- Issued
- Nov 17, 2020
- Abate by
- Jan 6, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.147(c)(6)(i):The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed: (a) On or about June 10, 2020, an annual/periodic inspection of the energy control procedures has not been conducted for, but not limited to HVAC systems, fans, boilers, air compressors and building systems to ensure that procedures and requirements of the standard are being followed and that employees who implement energy control procedures understand their application.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.147 D02
- Issued
- Nov 17, 2020
- Abate by
- Jan 6, 2021
- Penalty
- Initial $8,193 · Current $5,407 Reduced
General-duty citation text
29 CFR 1910.147(d)(2): An orderly shutdown of machine or equipment was not utilized to avoid any additional or increased hazards to employees as a result of equipment stoppage: (a) Exhaust Fan #9, Building 1996 Basement: On or about May 13, 2020, the employer did not ensure the fan to the air handling intake was properly shut down, utilizing a hazardous energy control program procedure (Lockout/Tagout), exposing employee to caught-in and struck-by hazard, and amputation injury.
Recent events (2)
- — I (S) $5407
- — Z (S) $8193
1910.147 C04 II
- Issued
- Nov 12, 2020
- Abate by
- Jan 29, 2021
- Penalty
- Initial $13,494 · Current $5,436 Reduced
General-duty citation text
29 CFR 1910.147(c)(4)(ii): The procedures did not clearly and specifically outline the scope, purpose, authorization, rules, and techniques to be utilized for the control of hazardous energy, and the means to enforce compliance including, but not limited to, the following: On or about June 10, 2020, written machine/equipment specific energy control procedures for, but not limited to HVAC systems, fans, boilers, air compressors and other building systems, did not document all hazardous energy sources associated with machines and equipment serviced by maintenance employees, and how to verify the energy sources have been isolated prior to performing work. Equipment identified, but not limited to the below equipment, did not have all hazardous energy sources identified. (a) Specific energy control procedures for all "Air Compressor" equipment used in the facilities and serviced by maintenance employees and outside contractors, did not identify pneumatic/compressed air as an energy source and how to isolate the pneumatic/compressed air. This exposes maintenance employees to struck by injuries from compressed air. (b) Specific energy control procedures for the four (4) boilers used in the facilities and serviced by maintenance employees and outside contractors, did not identify steam/ steam pressure as an energy source and how to isolate the steam/steam pressure prior to performing work on the boiler system. This exposes maintenance employees to struck by hazard and burns from steam/steam pressure. (c) Specific energy control procedures for the four (4) boilers used in the facilities and serviced by maintenance employees and outside contractors, did not identify natural gas as an energy source and how to isolate the gas prior to performing work on the boiler system. This exposes maintenance employees to struck by hazard and burns.
Recent events (2)
- — I (S) $5436
- — Z (S) $13494
More inspections at The Lutheran Home, INC.
View The Lutheran Home, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 623110)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344782917.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.