OSHA Inspection: STRATEGIC FILTRATION INC

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of STRATEGIC FILTRATION INC in 2401 MEYER ROAD, SEABROOK, TX 77586 (NAICS 811412). OSHA activity number 344783436.

Watch Strategic Filtration INC — free Get an email when a new federal OSHA severe-injury report for Strategic Filtration INC is published. One employer, no account, unsubscribe in one click.
Site address
2401 MEYER ROAD
City
SEABROOK
State
TX
ZIP
77586
Mailing
2500 FAIRWAY PARK DR, HOUSTON, TX 77092
Inspection type
Federal Agency (M)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811412
Employees
18
Ownership type
A

10 citations on file for this inspection.

1910.147 C04 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3856.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  a)  At the jobsite, employees did not utilize lockout/tag out procedures exposing the employees to amputation hazards while servicing a Carrier 50TC-A06A2A6A0A0A0 HVAC unit that had not been de-energized.
Recent events (3)
  • — F (S) $0
  • — C (S) $3856
  • — Z (S) $3856

1910.147 D04 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.147(d)(4)(i): Lockout or tagout devices were not affixed to each energy isolating device by authorized employees:  a)  At the jobsite, lockout devices were not affixed to a Carrier 50TC-A06A2A6A0A0A0 HVAC unit prior to maintenance, exposing employees to amputation hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.147 C06 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3856.00 · Current $0.00 Reduced
29 CFR 1910.147(c)(6)(i): The employer did not conduct a periodic inspection of the energy control procedure at least annually to ensure that the procedure and the requirement of this standard were being followed:  a)  At the jobsite, employees performing maintenance work on a Carrier 50TC-A06A2A6A0A0A0 HVAC unit were exposed to amputation hazards when the employer did not annually inspect the employer's written energy control procedure.
Recent events (3)
  • — F (S) $0
  • — C (S) $3856
  • — Z (S) $3856

1910.147 C07 III A

Serious Gravity 5 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $3856.00 · Current $2000.00 Reduced
29 CFR 1910.147(c)(7)(iii)(A): Retraining was not provided for authorized and affected employees when there was a change in their job assignments, a change in machines, equipment or processes that presented a new hazard, or when there was a change in the energy control procedures:   a)  At the jobsite, the employer did not instruct employees on the location of site-specific lockout points when servicing a Carrier 50TC-A06A2A6A0A0A0 HVAC unit at 2401 Meyer Road, Seabrook, Texas.
Recent events (3)
  • — F (S) $2000
  • — C (S) $3856
  • — Z (S) $3856

1910.304 G05

Other-than-serious Gravity 5 1 instance 1 exposed
Issued
Abate by
Penalty
Initial $3856.00 · Current $2000.00 Reduced
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  a)  At the jobsite, an employee was exposed to electric shock and electrocution hazards while using a Pullman-Holt Model 102 (Serial Number 5931) 120-volt Wet/Dry HEPA Vacuum with a missing plug grounding pin.
Recent events (3)
  • — F (O) $2000
  • — C (S) $3856
  • — Z (S) $3856

1910.305 G02 III

Other-than-serious Gravity 5 2 instances 1 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a) At the jobsite, an employee was exposed to electric shock and electrocution hazards while using a Pullman-Holt Model 102 (Serial Number 5931) 120-volt Wet/Dry HEPA Vacuum with strain relief damage to the plug.  b) At the jobsite, an employee was exposed to electric shock and electrocution hazards while using a Pullman-Holt Model 102 (Serial Number 5931) 120-volt Wet/Dry HEPA Vacuum with strain relief damage to the plug of the extension cord.
Recent events (3)
  • — F (O) $0
  • — C (S) $0
  • — Z (S) $0

1910.333 A01

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $5398.00 · Current $5000.00 Reduced
29 CFR 1910.333(a)(1): Live parts to which an employee may be exposed were not deenergized before an employee worked on or near them:  a)  At the worksite, a qualified person did not use test equipment to test the circuit elements and electrical parts of a Carrier Model 50TC-A06A2A6A0A0A0 480-Volt HVAC unit Serial Number 5114C89522, to which employees were exposed and did not verify that the circuit elements and equipment parts of the HVAC unit were de-energized.
Recent events (3)
  • — F (S) $5000
  • — C (S) $5398
  • — Z (S) $5398

1910.333 B02 II B

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on were not disconnected from all electric energy sources:  a)  At the worksite, a qualified person did not use test equipment to test the circuit elements and electrical parts of a Carrier Model 50TC-A06A2A6A0A0A0A0 480-volt HVAC unit serial number 5114C89522 to which employees were exposed and did not verify that the circuit elements and equipment parts of the HVAC unite were de energized.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.333 B02 III A

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2)(iii)(A): A lock and a tag were not placed on each disconnecting means used to deenergize circuits and equipment on which work was to be performed:  a)  At the worksite, a qualified person did not use test equipment to test the circuit elements and electrical parts of a Carrier Model 50TC-A06A2A6A0A0A0 480-volt HVAC unit Serial Number 5114C89522, to which employees were exposed and did not verify  that the circuit elements and equipment parts of the HVAC unit were de-energized.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.333 B02 IV B

Serious Gravity 10 1 instance 2 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR 1910.333(b)(2)(iv)(B):   Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed and did not verify that the circuit elements and equipment parts were de-energized:  a)  At the worksite, a qualified person did not use test equipment to test the circuit elements and electrical parts of a Carrier Model 50TC-A06A2A6A0A0A0 480-volt HVAC unit Serial Number 5114C89522, to which employees were exposed and did not verify that the circuit elements and equipment parts of the HVAC unit were de-energized.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

AEP