Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: RD HENRY & COMPANY LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of RD HENRY & COMPANY LLC in 3738 S. NORMAN ST., WICHITA, KS 67215 (NAICS 337110). OSHA activity number 344783923.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch RD Henry & Company LLC — free Get an email when a new federal OSHA severe-injury report for RD Henry & Company LLC is published. One employer, no account, unsubscribe in one click.
Site address
3738 S. NORMAN ST.
City
WICHITA
State
KS
ZIP
67215
Mailing
3738 S. NORMAN ST., WICHITA, KS 67215
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
337110
Employees
150
Ownership type
A

8 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 10 2 instances 2 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $12,145 · Current $6,073 Reduced
29 CFR 1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:    At 3738 S. Norman St, Wichita, KS, the employer had not ensured that specific energy control procedures were developed which contained electrical and pneumatic energy sources, exposing employees to electrical shock, amputation, caught-in, and struck by hazards in the following instances:     1) AKON 1440 A Edgebander S/N # 1000028864    2) BIESSE Rover CNC Router S/N # 1000031604
Recent events (2)
  • — I (S) $6072.5
  • — Z (S) $12145

1910.147 C07 I

Deleted Serious Gravity 5 2 instances 2 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $8,675 · Current $0 Reduced
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees:  At 3738 S. Norman St, Wichita, KS, the employer exposed employees to pneumatic and electrical hazardous energies in that employees were allowed to perform service and/or maintenance on equipment without first being trained to ensure those employees had the knowledge and skills for the safe application, usage, and removal of energy controls
Recent events (2)
  • — I (S) $0
  • — Z (S) $8675

1910.147 C06 II

Serious Gravity 5 2 instances 2 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $6,940 · Current $0 Reduced
29 CFR 1910.147(c)(6)(ii): The employer did not certify that periodic inspections of the energy control procedures had been performed:    At 3738 S. Norman St, Wichita, KS, the employer failed to conduct an annual or more frequent inspection of the energy control procedure and to ensure those employees had the knowledge[and skills for the safe application, usage, and removal of energy controls on all equipment used at facility in the following instances:     1) Big Mac Dust Collector P.D. Pump Model and S/N Unknown     2) Blum Hinger Minipress Model and S/N Unknown     3) Flat Line Oven Model and S/N Unknown     4) !/2" Dado Table Saw Model and S/N Unknown
Recent events (2)
  • — I (S) $0
  • — Z (S) $6940

1910.212 A03 II

Serious Gravity 10 4 instances 2 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $12,145 · Current $6,073 Reduced
29 CFR 1910.212(a)(3)(ii): Point of operation guards were not designed and constructed as to prevent the operator from having any part of their body in the danger zone during the operating cycle:    At 3738 S. Norman St, Wichita, KS, employees were exposed to amputation hazards.  Employees engaged in wood working activities were exposed to amputation hazards in that the point of operation was not guarded in the following instances:    1) CNC Machine: C.RONSRUD Model # 194HD18D S/N 3 19470401 (Deleted)  2) Dayton 20" Drill Press Model # 3Z919F S/N  Unknown     3) HOMAG Edgebander Model # KAL310/6/A20/S2 S/N 0-200-85-0048 (Deleted)
Recent events (2)
  • — I (S) $6072.5
  • — Z (S) $12145

1910.253 B02 II

Serious Gravity 5 1 instance 5 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $10,409 · Current $5,205 Reduced
29 CFR 1910.253(b)(2)(ii): Inside of buildings, cylinders were not stored in a well-protected, well-ventilated, dry location, at least 20 feet (6.1 m) from highly combustible materials such as oil or excelsior:    At 3738 S. Norman St, Wichita, KS in the Maintenance Shop, acetylene cylinders were stored less than a foot from oil, exposing employees to struck by and explosion hazards.
Recent events (2)
  • — I (S) $5204.5
  • — Z (S) $10409

1910.303 B01

Other-than-serious 1 instance 1 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $8,675 · Current $4,338 Reduced
29 CFR 1910.303(b)(1): Electrical equipment was not free from recognized hazards that were likely to cause death or serious physical harm to employees:     At 3738 S. Norman St, Wichita, KS, employees were exposed to electric shock. Employees engaged in woodworking activities were exposed to electric shock in that the Vertical Panel Saw power cord had exposed wires at the connector.
Recent events (2)
  • — I (O) $4337.5
  • — Z (S) $8675

1910.305 G01 IV A

Serious Gravity 1 1 instance 5 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $5,205 · Current $2,603 Reduced
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:    At 3738 S. Norman St, Wichita, KS, employees were exposed to fire and electrical shock hazards.  Employees engaged in maintenance activities in maintenance shop were exposed to fire and electrical shock hazards in that the flexible cord used to supply power to a Yuutool 13"x30" Metal Lathe S/N 190569  was used in lieu of fixed wiring.
Recent events (2)
  • — I (S) $2602.5
  • — Z (S) $5205

1910.305 G01 IV D

Deleted Serious Gravity 1 1 instance 5 exposed
Issued
Jul 20, 2020
Abate by
Aug 13, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces:  At 3738 S. Norman St, Wichita, KS, employees engaged in maintenance activities were exposed to electrical shock hazards in that a 110 volt flexible cord suppling power to an Yuutool 13" x 30" Metal Lathe S/N 190569 was secured to the building surface.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

View RD Henry & Company LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344783923.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.