On , OSHA opened a federal Agency safety inspection of WESTWOOD MANAGEMENT CORPORATION in 2805 NORTH UNIVERSITY DRIVE, WAUKESHA, WI 53186 (NAICS 531311). OSHA activity number 344831359.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Westwood Management Corporation — free Get an email when a new federal OSHA severe-injury report for Westwood Management Corporation is published. One employer, no account, unsubscribe in one click.
Site address
2805 NORTH UNIVERSITY DRIVE
City
WAUKESHA
State
WI
ZIP
53186
Mailing
9400 NORTH RANGE LINE ROAD, RIVER HILLS, WI 53217
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
531311
Employees
2
Ownership type
A

7 citations on file for this inspection.

1910.147 C01

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2020
Abate by
Mar 1, 2021
Penalty
Initial $5,398 · Current $4,300 Reduced
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  (a) On or about July 13, 2020, a written Energy Control Program (Lockout/Tagout) was not developed to ensure employee(s) who perform maintenance and repair work on HVAC units and other building systems, were not exposed to unexpected energizing, startup or release of stored energy from mechanical equipment.
Recent events (2)
  • — I (S) $4300
  • — Z (S) $5398

1910.147 C04 I

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2020
Abate by
Mar 1, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.147(c)(4)(i): Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  (a) On or about July 13, 2020, written procedures were not developed to ensure employee(s) who perform maintenance and repair work on HVAC units and other building systems, were not exposed to unexpected energizing, startup or release of stored energy from mechanical equipment.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C07 I

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2020
Abate by
Mar 1, 2021
Penalty
Initial $5,398 · Current $4,300 Reduced
29 CFR 1910.147(c)(7)(i): The employer did not provide adequate training to ensure that the purpose and function of the energy control program was understood by employees:  (a) On or about July 13, 2020, training was not provided to preventive maintenance personnel in the recognition of hazardous energy sources, the type of energy sources, and practices and methods required to safely deenergize machines/equipment, including but not limited to HVAC systems and other building equipment and systems.
Recent events (2)
  • — I (S) $4300
  • — Z (S) $5398

1910.332 B01

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2020
Abate by
Mar 1, 2021
Penalty
Initial $0 · Current $0
29 CFR 1910.332(b)(1): Employees were not trained in and familiar with the safety-related work practices required by 1910.331 through 1910.335 that pertained to their respective job assignments:  (a)  On or about July 13, 2020, maintenance employee(s) trouble shooting and repairing a Ducane Air Conditioning Unit (Model No. AC10B24 & Serial No. 6513090551), were not trained to assess the arc flash and shock hazard level of the electrical equipment being worked on.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 A02

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 18, 2020
Abate by
Mar 1, 2021
Penalty
Initial $5,398 · Current $4,300 Reduced
29 CFR 1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:  (a)  On or about July 13, 2020, a maintenance employee trouble shooting and repairing a Ducane Air Conditioning Unit (Model No. AC10B24 & Serial No. 6513090551) was exposed to electrical hazards.  The employer did not ensure electrical safe work practices were employed.
Recent events (2)
  • — I (S) $4300
  • — Z (S) $5398

1910.333 B02 II A

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 18, 2020
Abate by
Jan 25, 2021
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(ii)(A): Safe procedures for deenergizing circuits and equipment were not determined before circuits and equipment were deenergized.  (a)  On or about July 13, 2020, safe deenergization procedures were not developed and provided to maintenance employee(s) trouble shooting and repairing a Ducane Air Conditioning Unit (Model No. AC10B24 & Serial No. 6513090551), exposing the employee to an electrical shock hazard.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.333 B02 II C

Serious Gravity 10 1 instance 1 exposed
Issued
Dec 18, 2020
Abate by
Dec 31, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.333(b)(2)(ii)(C): Stored electric energy which might endanger personnel was not released.  Capacitors were not discharged and high capacitance elements were not short-circuited and grounded.  (a)  On or about July 13, 2020, a maintenance employee trouble shooting and repairing a Ducane Air Conditioning Unit (Model No. AC10B24 & Serial No. 6513090551) did not deenergize capacitor(s) associated with the air conditioner unit.  This exposed employee to an electrical shock hazard.