Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OHIO VALLEY ELECTRIC CORPORATION

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of OHIO VALLEY ELECTRIC CORPORATION in 5758 STATE ROUTE 7 NORTH, CHESHIRE, OH 45620 (NAICS 221112). OSHA activity number 344864681.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Ohio Valley Electric Corporation — free Get an email when a new federal OSHA severe-injury report for Ohio Valley Electric Corporation is published. One employer, no account, unsubscribe in one click.
Site address
5758 STATE ROUTE 7 NORTH
City
CHESHIRE
State
OH
ZIP
45620
Mailing
P.O. BOX 468, PIKETON, OH 45661
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221112
Employees
224
Ownership type
A

7 citations on file for this inspection.

1910.269 A02 I A

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Abate by
Dec 31, 2020
Penalty
Initial $13,494 · Current $8,771 Reduced
29 CFR 1910.269(a)(2)(i)(A): Each employee shall be trained in, and familiar with, the safety-related work practices, safety procedures, and other safety requirements in this section that pertain to his or her job assignments.   a. On or about August 3, 2020, the employer did not ensure that employees performing troubleshooting and repair work on a 4,000 volt breaker followed established practices for the control of arc flash hazards
Recent events (2)
  • — I (S) $8771.1
  • — Z (S) $13494

1910.269 C01 II

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Penalty
Initial $13,494 · Current $8,771 Reduced
29 CFR 1910.269(c)(1)(ii): The employer shall ensure that the employee in charge conducts a job briefing that meets paragraphs (c)(2), (c)(3), and (c)(4) of this section with the employees involved before they start each job.   a. On or about August 3, 2020, the employer did not ensure that a job briefing was conducted prior to employees performing troubleshooting and repair work on a 4,000 volt breaker.
Recent events (2)
  • — I (S) $8771.1
  • — Z (S) $13494

1910.269 D06

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Penalty
Initial $13,494 · Current $8,771 Reduced
29 CFR 1910.269(d)(6): The established procedures for the application of energy control (the lockout or tagout procedures) shall include the following elements and actions, and these procedures shall be performed as required by 29 CFR 1910.269(d)(6)(i) through (d)(6)(vii).    a. On or about August 3, 2020, employees were exposed to electrical arc flash and shock hazards during troubleshooting and repair work performed on an energized 4,000 volt Pulverizer & Pulverizer Fan No. 6 breaker. The employer did not ensure that energy control applications steps were implemented as the switchgear buss was not de-energized to perform the work [per the 1910.269(d)(6)(ii) requirements]. As a result, the remaining applicable energy control elements, involving electrical energy isolation [(d)(6)(iii)], LOTO device application [(d)(6)(iv), and verification of isolation [(d)(6)(vii)], were not implemented to protect employees from electrical hazards.
Recent events (2)
  • — I (S) $8771.1
  • — Z (S) $13494

1910.269 D08 II

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Penalty
Initial $0 · Current $0
29 CFR 1910.269(d)(8)(ii): When servicing or maintenance is performed by a crew, craft, department, or other group, they shall use a procedure which affords the employees a level of protection equivalent to that provided by the implementation of a personal lockout or tagout device. Group lockout or tagout devices shall be used in accordance with the procedures required by paragraphs (d)(2)(iii) and (d)(2)(iv) of this section.     a. On or about August 3, 2020, employees were exposed to electrical arc flash and shock hazards during troubleshooting and repair work performed on an energized 4,000 volt Pulverizer & Pulverizer Fan No. 6 breaker. The employer did not ensure that group lockout or tagout was performed.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.269 D02 IV

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Abate by
Nov 16, 2020
Penalty
Initial $13,494 · Current $0 Reduced
29 CFR 1910.269(d)(2)(iv): The procedure shall clearly and specifically outline the scope, purpose, responsibility, authorization, rules, and techniques to be applied to the control of hazardous energy, and the measures to enforce compliance including, but not limited to, 29 CFR 1910.269(d)(2)(iv)(A) through (d)(2)(iv)(D).  a.  On or about August 3, 2020 specific steps were not utilized to implement and verify the effectiveness of energy control procedures including steps for the placement, removal and transfer of lockout/tagout devices while working on the Unit 5 4KV B Buss breaker.�
Recent events (2)
  • — I (S) $0
  • — Z (S) $13494

1910.269 L03 III

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Penalty
Initial $13,494 · Current $8,771 Reduced
29 CFR 1910.269(l)(3)(iii): The employer shall ensure that no employee approaches or takes any conductive object closer to exposed energized parts than the employer's established minimum approach distance.   a. On or about August 3, 2020, employees were performing troubleshooting and repair work within the minimum approach distance of an energized 4,000 volt breaker, Pulverizer & Pulverizer Fan No. 6. Visual inspection and removal of breaker components by hand and with a non-insulated ratchet wrench exposed employees to an arc flash and electrical shock hazard.
Recent events (2)
  • — I (S) $8771.1
  • — Z (S) $13494

1910.269 L08 V

Serious Gravity 10 1 instance 3 exposed
Issued
Oct 9, 2020
Penalty
Initial $13,494 · Current $8,771 Reduced
29 CFR 1910.269(l)(8)(v): The employer shall ensure that each employee exposed to hazards from electric arcs wears protective clothing and other protective equipment with an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeds 2.0 cal/cm2. This protective equipment shall cover the employee's entire body.   a. On or about August 3, 2020, the employer did not ensure that employees utilized adequate personal protective equipment while performing troubleshooting and repair work on an energized 4,000 volt breaker, Pulverizer & Pulverizer Fan No. 6, thereby exposing employees to arc flash and blast hazards.
Recent events (2)
  • — I (S) $8771.1
  • — Z (S) $13494

View Ohio Valley Electric Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344864681.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.