Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,196,249Inspections Most recent open 2026-08-20 Last loaded 2026-08-24

OSHA Inspection: ABB ENTERPRISE SOFTWARE INC.

Unprogrammed Related inspection · Safety discipline

On , OSHA opened an unprogrammed Related safety inspection of ABB ENTERPRISE SOFTWARE INC. in NUCLEAR PLANT ROAD, ATHENS, AL 35611 (NAICS 237130). OSHA activity number 344902010.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ABB Enterprise Software INC. for free Get an email when a new federal OSHA severe-injury report for ABB Enterprise Software INC. is published. One employer, no account, unsubscribe in one click.
Site address
NUCLEAR PLANT ROAD
City
ATHENS
State
AL
ZIP
35611
Mailing
901 MAIN CAMPUS DRIVE, RALEIGH, NC 27606
Inspection type
Unprogrammed Related (G)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
Non-union (B)
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
237130
Employees
3
Ownership type
Private (A)

2 citations on file for this inspection.

1926.403 I02 I

Other-than-serious 1 instance 1 exposed
Issued
Sep 8, 2020
Penalty
Initial $8,848 · Current $8,848
29 CFR 1926.403(i)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by cabinets or other forms of enclosures, nor by any of the means listed in subparagraphs (A) through (D) of this paragraph:    (a) On or about 06/03/2020 - Cooling Tower Switchgear building, D4 cubicle, the 4000-Volt surge arrester panel did not have a protective cover installed to prevent contact with energized conductors.
Recent events (2)
  • · I (O) $8848
  • · Z (S) $8848

1926.416 A03

Other-than-serious 1 instance 1 exposed
Issued
Sep 8, 2020
Penalty
Initial $8,848 · Current $8,848
29 CFR 1926.416(a)(3): Employer did not advise employees of the location of energized electrical power circuits, the hazards involved, and the protective measures to be taken:    (a) On or about 06/03/2020 - Cooling Tower Switchgear building, D4 cubicle, employees installing insulating electrical boots on de-energized 5kV cubicles were not informed of the location of similar switchgear cubicles in the building  area that were energized.
Recent events (2)
  • · I (O) $8848
  • · Z (S) $8848

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 344902010.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.