Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,193,745Inspections Most recent open 2026-08-06 Last loaded 2026-08-10

OSHA Inspection: BELL NURSERY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BELL NURSERY in 2625 OLD CLIFTON RD., SPRINGFIELD, OH 45502 (NAICS 424930). OSHA activity number 344915046.

What this inspection record means

OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Bell Nursery for free Get an email when a new federal OSHA severe-injury report for Bell Nursery is published. One employer, no account, unsubscribe in one click.
Establishment
BELL NURSERY
Site address
2625 OLD CLIFTON RD.
City
SPRINGFIELD
State
OH
ZIP
45502
Mailing
7111 TROY HILL RD., ELKRIDGE, MD 21075
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424930
Employees
85
Ownership type
A

3 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 10 1 instance 2 exposed
Issued
Dec 1, 2020
Abate by
Dec 28, 2020
Penalty
Initial $9,446 · Current $9,446
29 CFR 1910.305(b)(1)(ii): (Cabinets, boxes, and fittings --- Conductors entering boxes, cabinets, or fittings)  Unused openings in boxes, cabinets, or fittings shall be effectively closed.  On September 4, 2020, located at the House 5 breaker panel, the employer did not effectively close an unused opening on a 120v/208v electrical service panel in that a breaker filler plate was missing on the interior panelboard of an I-T-E circuit breaker box, exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $9446
  • · Z (S) $9446

1910.305 G02 III

Serious Gravity 10 1 instance 3 exposed
Issued
Dec 1, 2020
Abate by
Dec 28, 2020
Penalty
Initial $9,446 · Current $0 Reduced
29 CFR  1910.305(g)(2)(iii): (Flexible cords and cables -- Identification, splices, and terminations) Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws.   On September 4, 2020, located at watering booms near row 10 in House 8, the employer did not provide strain relief to in-use electrical cords hanging off the booms,  in that electrical cord outer jackets were significantly damaged and not protecting interior conductors and insulators from water spray, exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $9446

1910.305 J02 IV

Serious Gravity 10 1 instance 3 exposed
Issued
Dec 1, 2020
Abate by
Dec 28, 2020
Penalty
Initial $9,446 · Current $0 Reduced
29 CFR  1910.305(j)(2)(iv): (Equipment for general use -- Receptacles, cord connectors, and attachment plugs (caps). A receptacle installed in a wet or damp location shall be suitable for the location.   On September 4, 2020, located throughout Houses 1B, 4, 6, and 7, at least 16 electrical outlets were installed in wet or damp locations (near watering booms or under a missing ceiling) that did not have weatherproof covers; were significantly damaged with exposed internal components; and/or not protected from weather and/or water sources, exposing employees to electrical hazards.
Recent events (2)
  • · I (S) $0
  • · Z (S) $9446

View Bell Nursery's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344915046.