Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MCCOLLUM ELECTRICAL SERVICES, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MCCOLLUM ELECTRICAL SERVICES, INC. in COASTAL DIAGNOSTICS 4674 AIRPORT BLVD #C, MOBILE, AL 36609 (NAICS 238210). OSHA activity number 344926720.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Mccollum Electrical Services, INC. — free Get an email when a new federal OSHA severe-injury report for Mccollum Electrical Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
COASTAL DIAGNOSTICS 4674 AIRPORT BLVD #C
City
MOBILE
State
AL
ZIP
36609
Mailing
2462 N. DOG RIVER DRIVE, MOBILE, AL 36605
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
30
Ownership type
A

2 citations on file for this inspection.

1926.416 A01

Serious Gravity 10 1 instance 3 exposed
Issued
Nov 23, 2020
Abate by
Dec 4, 2020
Penalty
Initial $9,446 · Current $5,750 Reduced
29 CFR 1926.416(a)(1): Employees were permitted to work in proximity to electric power circuits and were not protected against electric shock by de-energizing and grounding the circuits or effectively guarding the circuits by insulation or other means:  (a) Coastal Diagnostics 4674 Airport Blvd #C, rear of building: On or about August 24, 2020, the employer allowed employees to work in close proximity to energized 208 volt conductors while drilling a pilot hole for a knockout tool using a drill with a bit and chuck that were capable of damaging the insulation of the conductors without first de-energizing and grounding the circuits or effectively guarding the conductors using insulation or other means of protection capable of resisting damage from the drill chuck and bit.
Recent events (2)
  • — I (S) $5750
  • — Z (S) $9446

1904.39 A02

Other-than-serious 1 instance 1 exposed
Issued
Nov 23, 2020
Penalty
Initial $6,747 · Current $4,000 Reduced
29 CFR  1904.39(a)(2):The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye.  a) Coastal Diagnostics 4674 Airport Blvd #C:  On August 24, 2020, the employer had an employee suffer an electric shock while drilling an access hole in an electrical disconnect box requiring hospitalization.  The employer failed to report the work-related hospitalization to OSHA within twenty-four (24) hours.
Recent events (2)
  • — I (O) $4000
  • — Z (O) $6747

View Mccollum Electrical Services, INC.'s full OSHA safety record →