CAPE GIRARDEAU, MO ·
OSHA Inspection: RM COCO
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of RM COCO in 1389 SOUTHERN EXPRESSWAY, CAPE GIRARDEAU, MO 63701 (NAICS 314121). OSHA activity number 344946603.
OSHA opens inspections for many reasons: routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- RM COCO
- Site address
- 1389 SOUTHERN EXPRESSWAY
- City
- CAPE GIRARDEAU
- State
- MO
- ZIP
- 63701
- Mailing
- 1389 SOUTHERN EXPRESSWAY, CAPE GIRARDEAU, MO 63701
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- Non-union (B)
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 314121
- Employees
- 60
- Ownership type
- Private (A)
Citations
5 citations on file for this inspection.
1910.151 C
- Issued
- Oct 5, 2020
- Abate by
- Nov 16, 2020
- Penalty
- Initial $4,048 · Current $2,834 Reduced
General-duty citation text
29 CFR 1910.151(c): Where employees were exposed to injurious corrosive materials, suitable facilities for quick drenching or flushing of the eyes and body were not provided within the work area for immediate emergency use: In the forklift charging area, an eye wash was blocked by a drum on a pallet. (Note: eye wash equipment is required to be inspected, such as monthly and should be documented.) Abatement documentation is required for this violation.
Recent events (2)
- · I (S) $2833.6
- · Z (S) $4048
1910.157 C01
- Issued
- Oct 5, 2020
- Penalty
- Initial $4,048 · Current $2,834 Reduced
General-duty citation text
29 CFR 1910.157(c)(1): Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries: In the north area by the folding table a portable fire extinguisher was blocked by a cart.
Recent events (2)
- · I (S) $2833.6
- · Z (S) $4048
1910.157 G01
- Issued
- Oct 5, 2020
- Abate by
- Nov 16, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.157(g)(1): An educational program was not provided for all employees to familiarize them with the general principles of fire extinguisher use and the hazards involved with incipient stage fire fighting: There was no training on whether employees were to use portable fire extinguishers or only to evacuate. Training was not provided on the use of portable fire extinguishers. (Note: the emergency evacuation route plan, did not include a meeting place for employees once they exited the building.) Abatement documentation is required for this violation.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.303 B02
- Issued
- Oct 5, 2020
- Abate by
- Nov 16, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: At the warehouse cutting tables, equipment, including cooling fans and the cutting table were powered with multiple extension cords and power taps plugged into each other. (Note: power taps were required to be connected directly to building wiring outlets or drop down outlets. The surge manual states: "Connect the UPS power cable directly to a wall outlet." The manual also requires that not to operate with dust buildup, "excessive dust..." At the time of the inspection lint/dust was laying on the power taps and cord connections.) Abatement documentation is require for this violation.
Recent events (2)
- · I (S) $0
- · Z (S) $0
1910.305 G01 IV A
- Issued
- Oct 5, 2020
- Abate by
- Nov 16, 2020
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: At the warehouse cutting tables equipment, including cooling fans and the cutting table were powered with multiple extension cords and power taps plugged into each other. Abatement documentation is require for this violation.
Recent events (2)
- · I (S) $0
- · Z (S) $0
More inspections at RM Coco
View RM Coco's full OSHA safety record →
More inspections in this industry (NAICS 314121)
More inspections in MO
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). OSHA publishes its own view of this case as inspection number 344946603.