Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ST. THOMAS STEEL, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of ST. THOMAS STEEL, INC. in 19010 W. HWY 72, ARVADA, CO 80007 (NAICS 332312). OSHA activity number 344966387.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch ST. Thomas Steel, INC. — free Get an email when a new federal OSHA severe-injury report for ST. Thomas Steel, INC. is published. One employer, no account, unsubscribe in one click.
Site address
19010 W. HWY 72
City
ARVADA
State
CO
ZIP
80007
Mailing
19010 W. HWY 72, ARVADA, CO 80007
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332312
Employees
18
Ownership type
A

3 citations on file for this inspection.

1910.303 B02

Other-than-serious Gravity 1 1 instance 5 exposed
Issued
Nov 13, 2020
Abate by
Dec 18, 2020
Penalty
Initial $1,770 · Current $1,770
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a)St. Thomas Steel, Inc. at 19010 Highway 72 Arvada, CO 80007: On or before 10/8/2020, the employer did not ensure that power strips and extension cords were used in the manner they were designed. Power strips and extension cords were daisy-chained near the Piranha ironworker.
Recent events (2)
  • — I (O) $1770
  • — Z (S) $1770

1910.303 G01 I

Other-than-serious Gravity 1 1 instance 5 exposed
Issued
Nov 13, 2020
Abate by
Dec 18, 2020
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(i): The dimension of the working space in the direction of access to live parts operating at 600 volts or less and likely to require examination, adjustment, servicing, or maintenance while alive was less than indicated in Table S1:   (a)St. Thomas Steel, Inc. at 19010 Highway 72 Arvada, CO 80007: On or before 10/8/2020, the employer did not ensure that adequate spacing was provided for electrical service panels in the shop. Various items were stored within the prescribed space.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.305 J02 V

Other-than-serious Gravity 1 1 instance 5 exposed
Issued
Nov 13, 2020
Abate by
Dec 18, 2020
Penalty
Initial $0 · Current $0
29 CFR  1910.305(j)(2)(v): A receptacle installed outdoors in a location protected from the weather or in other damp locations did not have an enclosure for the receptacle that was weatherproof when the receptacle was covered (attachment plug cap not inserted and receptacle covers closed):  (a)St. Thomas Steel, Inc. at 19010 Highway 72 Arvada, CO 80007: On or before 10/8/2020, the employer did not ensure that the 20 amp duplex outlet located in the outdoor painting area was covered in accordance with this standard.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

View ST. Thomas Steel, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 344966387.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.