Safety Incidents OSHA Severe Injury Reports · 2015–2025
4,113,118Inspections Most recent open 2026-07-13 Last loaded 2026-07-17

OSHA Inspection: C C AMERICAN OILFIELD, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of C C AMERICAN OILFIELD, LLC in 4826 SANTA ELENA ST, CORPUS CHRISTI, TX 78405 (NAICS 333132). OSHA activity number 345024434.

Watch C C American Oilfield, LLC — free Get an email when a new federal OSHA severe-injury report for C C American Oilfield, LLC is published. One employer, no account, unsubscribe in one click.
Site address
4826 SANTA ELENA ST
City
CORPUS CHRISTI
State
TX
ZIP
78405
Mailing
PO BOX 260012, CORPUS CHRISTI, TX 78426
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
333132
Employees
18
Ownership type
A

4 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 5 instances 7 exposed
Issued
Abate by
Penalty
Initial $7802.00 · Current $7802.00
29 CFR  1910.305(b)(1)(ii):  Unused openings in boxes, cabinets, or fittings were not effectively closed:  At this establishment, electric circuit panels and electrical outlets had unused openings in the following instances:  a.  main shop building, two electric circuit panels had openings on the bottom of the panels; b.  main shop building, an electrical panel had a missing circuit breaker #20; c.  drill press shop, an electrical outlet had an opening on the bottom of the outlet box; d.  code shop, an electrical circuit panel missing blanks/breakers #5, #6, and #9, and a second electrical circuit panel missing blanks/breakers #15 and #16; and, e.  code shop, a Square D general duty safety switch, 100A, 240V, for a Flextec 650X welder, had an opening on the bottom of the box.
Recent events (1)
  • — Z (S) $7802

1910.303 F02

Other-than-serious 2 instances 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.303(f)(2):  Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  In the code shop, electric circuit breakers were not marked as to their function or purpose in the following instances:  a.  electrical circuit panel missing breakers #5, #6, and #9, and b.  electrical circuit panel missing breakers #15 and #16.
Recent events (1)
  • — Z (O) $0

1910.304 G05

Other-than-serious 1 instance 5 exposed
Issued
Abate by
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.304(g)(5):  The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective:  In the drill press shop, the Rigid Model 535 pipe threader electrical cord was missing the ground prong.
Recent events (1)
  • — Z (O) $0

1910.1200 F06 I

Other-than-serious 1 instance 5 exposed
Issued
Penalty
Initial $0.00 · Current $0.00
29 CFR  1910.1200(f)(6)(i):  Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the information required by 29 CFR 1910.1200(f)(1)(i) through 29 CFR 1910.1200(f)(1)(v):  At this establishment in the main shop building, the employer did not ensure all chemical containers were identified and labeled as to their contents.
Recent events (1)
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345024434.