Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: NAS COMMISSARY FALLON

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of NAS COMMISSARY FALLON in 4755 PASTURE ROAD, BLDG. 340 NAS FALLON, FALLON, NV 89496 (NAICS 445299). OSHA activity number 345026777.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NAS Commissary Fallon — free Get an email when a new federal OSHA severe-injury report for NAS Commissary Fallon is published. One employer, no account, unsubscribe in one click.
Site address
4755 PASTURE ROAD, BLDG. 340 NAS FALLON
City
FALLON
State
NV
ZIP
89496
Mailing
4755 PASTURE ROAD, B-340 NAS FALLON, FALLON, NV 89496
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
445299
Employees
31
Ownership type
D

2 citations on file for this inspection.

1910.159 C10

Serious Gravity 5 1 instance 1 exposed
Issued
Dec 9, 2020
Abate by
Jan 6, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.159(c)(10): The minimum vertical clearance of 18 inches between automatic sprinkler systems sprinklers and the material below was not maintained: 	 (a) On or about November 17, 2020 and at times prior to that date, for the employees exposed to fire hazards where items were stored on top of self in a storage closet six inch from a fire sprinkler head in the produce department located at 4755 Pasture Road Bldg. 340, Fallon Naval Air Station, Nevada.
Recent events (1)
  • — Z (S) $0

1910.303 G01

Repeat Gravity 5 1 instance 1 exposed
Issued
Dec 9, 2020
Abate by
Dec 21, 2020
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  (a) On or about November 17, 2020 and at times prior to that date, for the employees exposed to electrical hazards where electrical panel LB was blocked from access in a produce department room located at 4755 Pasture Road Bldg. 340, Fallon Naval Air Station, Nevada.  Notice number 2, Item number 1, 29 CFR 1910.303(g)(1) as required by 29 CFR 1960.8(b): Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment. The employer was cited for a violation of the similar standard and similar hazard on April 26, 2016, Inspection number 1135664, date May 26, 2016 of final order/settlement, and means of abatement.
Recent events (1)
  • — Z (R) $0

View NAS Commissary Fallon's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345026777.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.