OSHA Inspection: GOD'S MOUNTAIN RECOVERY CENTER

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of GOD'S MOUNTAIN RECOVERY CENTER in 94 ADAMS DRIVE, WAYMART, PA 18472 (NAICS 623220). OSHA activity number 345045942.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch God'S Mountain Recovery Center — free Get an email when a new federal OSHA severe-injury report for God'S Mountain Recovery Center is published. One employer, no account, unsubscribe in one click.
Site address
94 ADAMS DRIVE
City
WAYMART
State
PA
ZIP
18472
Mailing
94 ADAMS DRIVE, WAYMART, PA 18472
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623220
Employees
3
Ownership type
A

2 citations on file for this inspection.

1910.305 B01 II

Serious Gravity 5 3 instances 1 exposed
Issued
Jan 28, 2021
Abate by
Mar 17, 2021
Penalty
Initial $1,990 · Current $1,990
29 CFR  1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed:   a) Pantry: An unused opening (knockout) located at the bottom right hand side of panel #1 was not effectively closed, as observed on or about December 3, 2020.  b) Pantry: An unused opening (knockout) located at the underside of panel #3 was not effectively closed, as observed on or about December 3, 2020.  c) Pantry: An unused opening (knockout) located on the center face of a 12 volt (DC) Direct Current  step down transformer box was not effectively closed, as observed on or about December 3, 2020.  ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $1990

1910.303 F02

Serious Gravity 1 3 instances 1 exposed
Issued
Jan 28, 2021
Abate by
Feb 24, 2021
Penalty
Initial $1,492 · Current $1,492
29 CFR  1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Pantry: The circuit breakers in the three (3) electrical panel boxes were not legibly marked to indicate their purpose, as observed on or about December 3, 2020.  ABATEMENT CERTIFICATION REQUIRED