Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: MX ELECTRIC, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of MX ELECTRIC, INC. in 301 S. VETERAN'S PARKWAY, NORMAL, IL 61761 (NAICS 238210). OSHA activity number 345054613.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch MX Electric, INC. — free Get an email when a new federal OSHA severe-injury report for MX Electric, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
MX ELECTRIC, INC.
Site address
301 S. VETERAN'S PARKWAY
City
NORMAL
State
IL
ZIP
61761
Mailing
403 S. EAST AVE., OGDEN, IL 61859
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
12
Ownership type
A

5 citations on file for this inspection.

1926.403 B01

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 7, 2021
Abate by
Apr 22, 2021
Penalty
Initial $5,461 · Current $5,000 Reduced
29 CFR 1926.403(b)(1): Employer did not ensure that electrical equipment is free from recognized hazards that are likely to cause death or serious physical harm to employees:  On or about December 8, 2020, employees were exposed to electrical hazards while using a temporary electrical panel and the employer did not ensure that electrical equipment was examined, in order to identify hazards.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5461

1926.405 A02 II H

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 7, 2021
Abate by
Apr 22, 2021
Penalty
Initial $5,461 · Current $0 Reduced
29 CFR  1926.405(a)(2)(ii)(H):A box was not used in temporary wiring when a change was made to a raceway system or a cable system which was metal clad or metal sheath:  On or about December 8, 2020 employees were exposed to electrical shock and burns while using temporary wiring and the employer did not ensure that a box was used when there was a change made to the raceway system.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5461

1926.405 G02 IV

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 7, 2021
Abate by
Apr 22, 2021
Penalty
Initial $5,461 · Current $0 Reduced
29 CFR  1926.405(g)(2)(iv):Flexible cords were not connected to devices and fittings so that strain relief is provided to prevent pull from being directly transmitted to joints or terminal screws:  On or about December 8, 2021, employees were exposed to electrical hazards while utilizing a temporary power panel and the employer did not ensure that flexible cords coming out of the panel box were provided with strain relief.
Recent events (2)
  • — I (S) $0
  • — Z (S) $5461

1926.405 B02

Serious Gravity 10 1 instance 1 exposed
Issued
Apr 7, 2021
Abate by
Apr 22, 2021
Penalty
Initial $5,461 · Current $5,000 Reduced
29 CFR  1926.405(b)(2):In energized installations, each outlet box did not have a cover, faceplate, or fixture canopy:  On or about December 8, 2020, employees were exposed to electrical hazards when utilizing temporary outlets and the employer did not ensure that each outlet box was equipped with a cover or faceplate.
Recent events (2)
  • — I (S) $5000
  • — Z (S) $5461

1926.405 G02 V

Deleted Serious Gravity 10 1 instance 1 exposed
Issued
Apr 7, 2021
Abate by
Apr 22, 2021
Penalty
Initial $0 · Current $0
29 CFR  1926.405(g)(2)(v):Flexible cords and cables were not protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures:  On or about December 8, 2020, employees were exposed to electrical hazards while utilizing a temporary power panel and the employer did not ensure that the flexible cords passing through a hole in the bottom were protected by bushings or fittings.