KALISPELL, MT —
OSHA Inspection: OHS AUTO BODY, INC.
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of OHS AUTO BODY, INC. in 3560 HWY 93 SOUTH, KALISPELL, MT 59901 (NAICS 811121). OSHA activity number 345056394.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- OHS AUTO BODY, INC.
- Site address
- 3560 HWY 93 SOUTH
- City
- KALISPELL
- State
- MT
- ZIP
- 59901
- Mailing
- PO BOX 8566, KALISPELL, MT 59904
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 811121
- Employees
- 45
- Ownership type
- A
Citations
5 citations on file for this inspection.
1910.303 B07 I
- Issued
- May 12, 2021
- Abate by
- Jun 8, 2021
- Penalty
- Initial $3,481 · Current $3,481
General-duty citation text
29 CFR 1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment: a) OHS' Body Shop, Body Technician Assembly Area, North Wall Panel B Electrical Breaker Box: On or about December 8, 2020 and at times prior, employees were exposed to electrical shock and fire hazards while working near an electrical breaker panel that was missing a knock out.
Recent events (1)
- — Z (S) $3481
1910.305 J01 IV
- Issued
- May 12, 2021
- Abate by
- Jun 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(1)(iv):Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lamp holders or other electrical parts: a) OHS's Body Shop, Detail Bay: On or about December 8, 2020 and at times prior, employees were exposed to electrical shock hazards while washing automobiles in the detail wash bay that contained florescent tube lights without weatherproof covers.
Recent events (1)
- — Z (S) $0
1910.305 J02 IV
- Issued
- May 12, 2021
- Abate by
- Jun 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(j)(2)(iv):A receptacle installed in a wet or damp location was not suitable for the location: a) OHS's Body Shop, Detail Bay: On or about December 8, 2020 and at times prior, employees were exposed to electrical shock hazards while utilizing an electrical receptacle located in the detail wash bay that did not contain a weatherproof front cover.
Recent events (1)
- — Z (S) $0
1910.107 B09
- Issued
- May 12, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.107(b)(9):A clear space of not less than 3 feet on all sides was not kept free from storage or combustible construction: a) OHS' Body Shop, Spray Booth: On or about December 8, 2020 and at times prior, the employer failed to maintain cleaning distance around spray booth in that boxes were stored in direct proximity to the paint booth wall while employees are working in and around the paint booth.
Recent events (1)
- — Z (O) $0
1910.303 G01
- Issued
- May 12, 2021
- Abate by
- Jun 8, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment: a) OHS' Body Shop, Body Technician Assembly Area, North Wall Panel B Electrical Breaker Panel: On or about December 8, 2020 and at times prior, the employer failed to ensure that the area around the electrical panel was clear to make it easily accessible in the event of an emergency. b) OHS' Body Shop, Water Cooler/Soda Machine Area, West Wall Electrical Breaker Panel: On or about December 8, 2020 and at times prior, the employer failed to ensure that the area around the electrical panel was clear to make it easily accessible in the event of an emergency.
Recent events (1)
- — Z (O) $0
More inspections at OHS Auto Body, INC.
View OHS Auto Body, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 811121)
More inspections in MT
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345056394.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.