Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OHS AUTO BODY, INC.

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of OHS AUTO BODY, INC. in 3560 HWY 93 SOUTH, KALISPELL, MT 59901 (NAICS 811121). OSHA activity number 345056394.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch OHS Auto Body, INC. — free Get an email when a new federal OSHA severe-injury report for OHS Auto Body, INC. is published. One employer, no account, unsubscribe in one click.
Establishment
OHS AUTO BODY, INC.
Site address
3560 HWY 93 SOUTH
City
KALISPELL
State
MT
ZIP
59901
Mailing
PO BOX 8566, KALISPELL, MT 59904
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811121
Employees
45
Ownership type
A

5 citations on file for this inspection.

1910.303 B07 I

Serious Gravity 1 1 instance 17 exposed
Issued
May 12, 2021
Abate by
Jun 8, 2021
Penalty
Initial $3,481 · Current $3,481
29 CFR  1910.303(b)(7)(i):Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment:  a)  OHS' Body Shop, Body Technician Assembly Area, North Wall Panel B Electrical Breaker Box:  On or about December 8, 2020 and at times prior, employees were exposed to electrical shock and fire hazards while working near an electrical breaker panel that was missing a knock out.
Recent events (1)
  • — Z (S) $3481

1910.305 J01 IV

Serious Gravity 1 1 instance 1 exposed
Issued
May 12, 2021
Abate by
Jun 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(j)(1)(iv):Fixtures installed in wet or damp locations were not approved for the purpose and were not so constructed or installed that water could not enter or accumulate in wireways, lamp holders or other electrical parts:  a) OHS's Body Shop, Detail Bay: On or about December 8, 2020 and at times prior, employees were exposed to electrical shock hazards while washing automobiles in the detail wash bay that contained florescent tube lights without weatherproof covers.
Recent events (1)
  • — Z (S) $0

1910.305 J02 IV

Serious Gravity 1 1 instance 1 exposed
Issued
May 12, 2021
Abate by
Jun 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(j)(2)(iv):A receptacle installed in a wet or damp location was not suitable for the location:  a) OHS's Body Shop, Detail Bay: On or about December 8, 2020 and at times prior, employees were exposed to electrical shock hazards while utilizing an electrical receptacle located in the detail wash bay that did not contain a weatherproof front cover.
Recent events (1)
  • — Z (S) $0

1910.107 B09

Other-than-serious 1 instance 17 exposed
Issued
May 12, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.107(b)(9):A clear space of not less than 3 feet on all sides was not kept free from storage or combustible construction:  a)  OHS' Body Shop, Spray Booth:  On or about December 8, 2020 and at times prior, the employer failed to maintain cleaning distance around spray booth in that boxes were stored in direct proximity to the paint booth wall while employees are working in and around the paint booth.
Recent events (1)
  • — Z (O) $0

1910.303 G01

Other-than-serious 2 instances 17 exposed
Issued
May 12, 2021
Abate by
Jun 8, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1):Sufficient access and working space was not provided and maintained about all electric equipment (operating at 600 volts, nominal, or less to ground) to permit ready and safe operation and maintenance of such equipment:  a)  OHS' Body Shop, Body Technician Assembly Area, North Wall Panel B Electrical Breaker Panel:  On or about December 8, 2020 and at times prior, the employer failed to ensure that the area around the electrical panel was clear to make it easily accessible in the event of an emergency.  b)  OHS' Body Shop, Water Cooler/Soda Machine Area, West Wall Electrical Breaker Panel:  On or about December 8, 2020 and at times prior, the employer failed to ensure that the area around the electrical panel was clear to make it easily accessible in the event of an emergency.
Recent events (1)
  • — Z (O) $0

View OHS Auto Body, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345056394.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.