Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: THE MARTIN-BROWER COMPANY, LLC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of THE MARTIN-BROWER COMPANY, LLC in 191 MOODY ROAD, ENFIELD, CT 06082 (NAICS 424410). OSHA activity number 345109045.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Martin-Brower Company, LLC — free Get an email when a new federal OSHA severe-injury report for The Martin-Brower Company, LLC is published. One employer, no account, unsubscribe in one click.
Site address
191 MOODY ROAD
City
ENFIELD
State
CT
ZIP
06082
Mailing
191 MOODY ROAD, ENFIELD, CT 06082
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424410
Employees
215
Ownership type
A

5 citations on file for this inspection.

1910.22 A01

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Mar 31, 2021
Abate by
May 17, 2021
Penalty
Initial $4,973 · Current $0 Reduced
29 CFR  1910.22(a)(1):29 CFR 1910.22(a)(1): The employer did not ensure that all places of employment, passageways, storerooms, service rooms, and walking-working surfaces are kept in a clean, orderly, and sanitary condition.  Fire Pump Room:  On or about January 21, 2021,  access to control valves for the fire suppression system was impeded by the storage of items in front of them, subjecting employees to prolonged exposure to fire conditions in the event access to the controls was necessary.
Recent events (2)
  • — I (S) $0
  • — Z (S) $4973

1910.303 G01 II

Serious Gravity 1 1 instance 2 exposed
Issued
Mar 31, 2021
Abate by
May 17, 2021
Penalty
Initial $0 · Current $3,500
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  Electrical Room: On or about January 21, 2021,  a metal storage rack was located 36 inches in front of a 480v Cutler-Hammer switchboard, G.O. No. HC216658, prolonging employee exposure to energized equipment in the event the switchboard would need to be accessed.  In accordance with 1910.303(g), Table S-1, Condition B, the required distance is 42 inches.
Recent events (2)
  • — I (S) $3500
  • — Z (S) $0

1910.304 F01 IV

Deleted Serious Gravity 1 1 instance 3 exposed
Issued
Mar 31, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.304(f)(1)(iv):Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel:  Pallet Jack Charging Area: On or about January 21, 2021,  evaporator # 8 disconnect switch was blocked by pallet storage, prolonging employees exposure to energized equipment, in the event it would need to be de-energized.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.106 B04 IV G

Other-than-serious 1 instance 3 exposed
Issued
Mar 31, 2021
Abate by
Aug 30, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.106(b)(4)(iv)(g): The inlet of the fill pipe shall be located outside of buildings at a location free from any source of ignition and not less than 5 feet away from any building opening. The inlet of the fill pipe shall be closed and liquidtight when not in use. The fill connection shall be properly identified.   Fire Pump Room, Diesel Tank:  On or about January 21, 2021, the fill pipe provided on the 281 gallon fire pump tank was located inside the building.  The tank contained diesel fuel, a Category 3 flammable liquid.
Recent events (6)
  • — P (O) $0
  • — P (O) $0
  • — P (O) $0

1910.1200 F06 II

Other-than-serious 1 instance 1 exposed
Issued
Mar 31, 2021
Abate by
May 17, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(f)(6)(ii): Except as provided in 29 CFR 1910.1200(f)(7) and 29 CFR 1910.1200(f)(8), the employer did not ensure that each container of hazardous chemicals in the workplace was labeled, tagged or marked with the product identifier and words, pictures, symbols, or combination thereof, which provide at least general information regarding the hazards of the chemicals and which, in conjunction with the other information immediately available to employees under the hazard communication program, would provide employees with the specific information regarding the physical and health hazards of the hazardous chemical.  Fire Pump Room: On or about January 21, 2021,  a diesel tank with a volume of 281 gallons was found to be missing appropriate labeling, thereby not informing employees of the associated flammability hazards, skin irritation hazards, inhalation hazards, carcinogenic hazards and possibly exposing employees to the same.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View The Martin-Brower Company, LLC's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345109045.