Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: BALSAM MILLWORK AND CABINET, INC.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of BALSAM MILLWORK AND CABINET, INC. in 524 SAINT CROIX AVENUE, NEW RICHMOND, WI 54017 (NAICS 321918). OSHA activity number 345147714.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Balsam Millwork and Cabinet, INC. — free Get an email when a new federal OSHA severe-injury report for Balsam Millwork and Cabinet, INC. is published. One employer, no account, unsubscribe in one click.
Site address
524 SAINT CROIX AVENUE
City
NEW RICHMOND
State
WI
ZIP
54017
Mailing
524 SAINT CROIX AVENUE, NEW RICHMOND, WI 54017
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
321918
Employees
12
Ownership type
A

14 citations on file for this inspection.

1910.23 C11

Deleted Serious Gravity 1 1 instance 2 exposed
Issued
Aug 10, 2021
Abate by
Aug 31, 2021
Penalty
Initial $2,340 · Current $0 Reduced
29 CFR 1910.23(c)(11): The employer did not ensure that portable ladders used to gain access to an upper landing surface have side rails that extend at least 3 feet (0.9 m) above the upper landing surface.   (a) Main shop area; Side rails of a fiberglass extension ladder did not extend at least  three feet above the mezzanine storage area's upper landing surface.
Recent events (3)
  • — F (S) $0
  • — C (S) $2340
  • — Z (S) $2340

1910.28 B01 I

Deleted Serious Gravity 5 1 instance 2 exposed
Issued
Aug 10, 2021
Abate by
Aug 31, 2021
Penalty
Initial $3,901 · Current $0 Reduced
29 CFR 1910.28(b)(1)(i):  Except as provided elsewhere in this section 29 CFR 1910.28, the employer did not ensure that each employee on a walking-working surface with an unprotected side or edge that is 4 feet (1.2 m) or more above a lower level is protected from falling by one or more of the systems described in 29 CFR 1910.28(b)(1)(i):  (a) Main shop area; A means of fall protection was not provided for edges of an elevated mezzanine storage area.
Recent events (3)
  • — F (S) $0
  • — C (S) $3901
  • — Z (S) $3901

1910.147 C01

Serious Gravity 10 1 instance 4 exposed
Issued
Aug 10, 2021
Abate by
Jan 28, 2022
Penalty
Initial $5,461 · Current $1,000 Reduced
29 CFR  1910.147(c)(1):The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  (a) Throughout the facility;  An energy control program with procedures, employee training, and periodic inspections was not established and implemented before employees performed covered activities of machine setup and blade changes on equipment including, but not limited to, a gang ripsaw, planer, wide belt sander,  end-matcher, and table saw.
Recent events (3)
  • — F (S) $1000
  • — C (S) $5461
  • — Z (S) $5461

1910.178 F02

Serious Gravity 1 2 instances 3 exposed
Issued
Aug 10, 2021
Penalty
Initial $2,340 · Current $1,000 Reduced
29 CFR  1910.178(f)(2):The storage and handling of liquefied petroleum gas fuel shall be in accordance with NFPA Storage and Handling of Liquefied Petroleum Gases (NFPA No. 58-1969), which is incorporated by reference as specified in Sec. 1910.6.  (a) Rough mill area; A cylinder of liquid propane gas stored near the exit route and overhead door was exposed to physical damage or tampering (NFPA 58, section 8.2.1.1).  (b) Rough mill area; A cylinder of liquid propane gas was stored near an exit route (NFPA 58, section 8.2.1.3).
Recent events (3)
  • — F (S) $1000
  • — C (S) $2340
  • — Z (S) $2340

1910.212 A01

Serious Gravity 5 1 instance 1 exposed
Issued
Aug 10, 2021
Abate by
Aug 26, 2021
Penalty
Initial $3,121 · Current $1,000 Reduced
29 CFR  1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  (a) Main building; A Delta brand drill press was not equipped with guarding to protect against flying chips and rotating parts of the chuck and drill bit while it was used to drill holes into metal.
Recent events (3)
  • — F (S) $1000
  • — C (S) $3121
  • — Z (S) $3121

1910.213 D01

Deleted Serious Gravity 5 1 instance 1 exposed
Issued
Aug 10, 2021
Penalty
Initial $3,901 · Current $0 Reduced
29 CFR  1910.213(d)(1): Circular handfed crosscut table saw(s) were not guarded by an automatically adjusting hood which completely enclosed that portion of the saw above the table and above the material being cut:  (a) Main building; A hood guard was not used to protect/enclose the upper portion of a saw blade on the Holz Her model 1243 table saw while it was being used to cut a sheet of medium-density fiberboard (MDF).
Recent events (3)
  • — F (S) $0
  • — C (S) $3901
  • — Z (S) $3901

1910.303 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 10, 2021
Abate by
Aug 26, 2021
Penalty
Initial $3,901 · Current $1,000 Reduced
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  (a) Rough mill, east end; Two relocatable power taps (surge protector strips) were series-connected (daisy-chained) to each other.
Recent events (3)
  • — F (S) $1000
  • — C (S) $3901
  • — Z (S) $3901

1910.304 B02

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 10, 2021
Abate by
Aug 26, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.304(b)(2): Outlet devices had an ampere rating less than the load being served:  (a) Rough mill, east end; The listed ampacity of portable relocatable power taps was exceeded by equipment plugged into it.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.334 A02 I

Serious Gravity 5 3 instances 3 exposed
Issued
Aug 10, 2021
Penalty
Initial $3,901 · Current $0 Reduced
29 CFR  1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket):   Flexible extension cord sets exposed to damage were not visually inspected for damage. (a) Rough mill, east end; The outer jacket insulation was damaged and grounding pin was missing on an extension cord set.  (b) Rough mill, east end; The grounding pin was missing on an extension cord set.  (c) Main building, west end of north wall; The outer jacket insulation was damaged and grounding pin was missing on an extension cord set.
Recent events (3)
  • — F (S) $0
  • — C (S) $3901
  • — Z (S) $3901

1910.334 A03 II

Serious Gravity 5 2 instances 2 exposed
Issued
Aug 10, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.334(a)(3)(ii): Attachment plugs and receptacles were connected or altered in a manner which prevented proper continuity of the electric equipment grounding conductor at the point where plugs were attached to receptacles:   (a) Rough mill, east end; The grounding pins were missing on two extension cord sets being used to provide electrical power to 120 volt equipment, such as a 12-inch compound miter saw and material lifting table.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.36 G02

Other-than-serious 1 instance 4 exposed
Issued
Aug 10, 2021
Abate by
Aug 26, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.36(g)(2):Exit access(es) were not at least 28 inches (71.1 cm) wide at all points.  (a) Main building, northeast end; The access route to an emergency exit door was reduced to 22 inches by metal stored near the doorway.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.178 L04 III

Other-than-serious 1 instance 3 exposed
Issued
Aug 10, 2021
Abate by
Sep 29, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.178(l)(4)(iii): An evaluation of each powered industrial truck operator's performance was not being conducted at least once every three years:  (a) Throughout the facility; Each forklift operator's ability to safely operate forklifts was not reevaluated within three years.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.178 L06

Other-than-serious 1 instance 2 exposed
Issued
Aug 10, 2021
Abate by
Sep 29, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.178(l)(6): The employer did not certify that each operator has been trained and evaluated as required by this paragraph (l):   (a) Throughout the facility; A certification of training was not maintained for each forklift operator.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 4 exposed
Issued
Aug 10, 2021
Abate by
Aug 26, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii): The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  (a) Main building, northeast end; Several pieces of metal were stored directly in front of electrical service panels.
Recent events (3)
  • — F (O) $0
  • — C (O) $0
  • — Z (O) $0