MILWAUKEE, WI —
OSHA Inspection: STAFF ELECTRIC CO., INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of STAFF ELECTRIC CO., INC. in 818 E MASON ST., MILWAUKEE, WI 53202 (NAICS 238210). OSHA activity number 345152128.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- STAFF ELECTRIC CO., INC.
- Site address
- 818 E MASON ST.
- City
- MILWAUKEE
- State
- WI
- ZIP
- 53202
- Mailing
- W133 N5030 CAMPBELL DR., MENOMONEE FALLS, WI 53051
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 238210
- Employees
- 3
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.333 A
- Issued
- Aug 6, 2021
- Abate by
- Aug 18, 2021
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.333(a)(2): Safety-related work practices were not employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. The specific safety-related work practices shall be consistent with the nature and extent of the associated electrical hazards: (a) On or about February 13 , 2021, employees performing electrical work on or around 13,2000 volt AC energized electrical circuits and equipment, did not employ electrical safety-related work practices while working on the Russelectric 15,000 volt ATS #2 circuit breaker. This exposed employee(s) working at or around the circuit breaker to Arc-flash, electrical shock, and burns.
Recent events (3)
- — F (S) $0
- — C (S) $13653
- — Z (S) $13653
1910.333 B02 II B
- Issued
- Aug 6, 2021
- Abate by
- Aug 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(ii)(B): The circuits and equipment to be worked on were not disconnected from all electric energy sources: (a) On or about February 13, 2021, employee(s) performing electrical work on or around the Russelectric 15000 volt ATS #2 circuit breaker did not deenergized and disconnect the circuit breaker from the 13,200 volt AC energy source supplying the energy to the unit, when employee(s) opened the circuit breaker panel door to inspect the inside electrical components. This exposed employee(s) working at or around the circuit breaker to Arc-flash, electrical shock, and burns. In the alternative... 29 CFR 1910.147(c)(4)(i): Procedures were not utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section: a) On or about February 13 , 2021, employees performing electrical work on or around the Russelectric 15000 volt ATS #2 circuit breaker did not utilize procedures to control hazardous electrical energy when employee(s) opened the circuit breaker panel door to inspect the inside electrical components. This exposed employee(s) working on or around the circuit breaker to Arc-flash, electrical shock, and burns.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.333 B02 IV B
- Issued
- Aug 6, 2021
- Abate by
- Aug 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.333(b)(2)(iv)(B): Before circuits or equipment was worked as deenergized, a qualified person did not use test equipment to test the circuit elements and electrical parts of equipment to which employees would be exposed. (a) On or about February 13, 2021, employee(s) performing electrical work on or around the Russelectric 15,000 volt ATS #2 circuit breaker did not test the electrical circuit to insure that it was in a de-energized state prior to conducting work on the 13,200 volt AC circuit. This exposed employee(s) working at or around the circuit breaker to Arc-flash, electrical shock, and burns.
Recent events (3)
- — F (S) $0
- — C (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Aug 6, 2021
- Abate by
- Aug 12, 2021
- Penalty
- Initial $13,653 · Current $0 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not using electrical protective equipment that was appropriate for the specific parts of the body to be protected and for the work to be performed: (a) On or about February 13, 2021, employee(s) working on and around an energized Russelectric 15,000 volt ATS #2 circuit breaker, supplied by a 13,200 volt AC circuit, did not use personal protective equipment, such as, but not limited to arc rated apparel, faceshield, and voltage-rated gloves to protect against arc flash hazards and electrical shock hazards. This exposed employee(s) working at or around the circuit breaker to Arc-flash, electrical shock, and burns.
Recent events (3)
- — F (S) $0
- — C (S) $13653
- — Z (S) $13653
More inspections at Staff Electric CO., INC.
View Staff Electric CO., INC.'s full OSHA safety record →
More inspections in this industry (NAICS 238210)
More inspections in WI
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345152128.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.