TOBYHANNA, PA —
OSHA Inspection: A POCONO COUNTRY PLACE
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of A POCONO COUNTRY PLACE in 112 COUNTRY PLACE DRIVE, TOBYHANNA, PA 18466 (NAICS 813990). OSHA activity number 345153670.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- A POCONO COUNTRY PLACE
- Site address
- 112 COUNTRY PLACE DRIVE
- City
- TOBYHANNA
- State
- PA
- ZIP
- 18466
- Mailing
- 112 COUNTRY PLACE DRIVE, TOBYHANNA, PA 18466
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 813990
- Employees
- 75
- Ownership type
- A
Citations
14 citations on file for this inspection.
1910.147 C01
- Issued
- Jun 8, 2021
- Abate by
- Jul 12, 2021
- Penalty
- Initial $9,557 · Current $0 Reduced
General-duty citation text
29 CFR 1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative: a) K&L Gate - A lockout tagout program was not established for employees performing work on a lift gate and energy control devices were not applied, exposing employees to live electrical, on or about February 16, 2021. Abatement certification and documentation required.
Recent events (3)
- — J (S) $0
- — C (S) $9557
- — Z (S) $9557
1910.303 B02
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $5,461 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and/or used in accordance with any instructions included in the listing or labeling:. a) Guard shack - In the bathroom, across from the sink, a relocatable power tap were mounted to the walls, on or about February 16, 2021. b) Guard shack - In the bathroom, adjacent to the sink, a relocatable power tap were mounted to the walls, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $5461
- — Z (S) $5461
1910.303 C03 I
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $5,461 · Current $1,366 Reduced
General-duty citation text
29 CFR 1910.303(c)(3)(i): All splices and joints and the free ends of the conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose. a) Guard shack - Above the door frame, the splices were not covered with insulation equivalent to that of the conductors, exposing employees to a shock hazard, on or about February 16, 2021. b) Guard shack - In the bathroom, the splices were not covered with insulation equivalent to that of the conductors, exposing employees to a shock hazard, on or about February 16, 2021. c) Guard shack - In the bathroom, near the relocatable power tap, the splices were not covered with insulation equivalent to that of the conductors, exposing employees to a shock hazard, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (O) $1366
- — C (S) $5461
- — Z (S) $5461
1910.303 E01 II
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $4,096 · Current $4,096
General-duty citation text
29 CFR 1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary: a) Guard shack - The breaker panel which controls the receptacles in the guard shack was not labeled, on or about February 16, 2021. b) Guard shack - The breaker panel, behind the entrance door, was not labeled, on or about February 16, 2021. c) Welcome Center - In the housekeeping closet, the breaker panels was not labeled, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $4096
- — C (S) $4096
- — Z (S) $4096
1910.303 F
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.303(f): Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: a) Guard shack - Inside the breaker panel, each service, feeder and branch circuit was not legibly marked to indicate its purpose, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.303 G02 I
- Issued
- Jun 8, 2021
- Abate by
- Jun 14, 2021
- Penalty
- Initial $9,557 · Current $3,500 Reduced
General-duty citation text
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, or by any of the following means identified in sub-paragraphs (A)through (D) of this paragraph: a) Guard shack - In the bathroom, the continental access panel was open, exposing employees to electrocution hazard, on or about February 16, 2021. Abatement certification and documentation required.
Recent events (3)
- — J (O) $3500
- — C (S) $9557
- — Z (S) $9557
1910.305 B02 I
- Issued
- Jun 8, 2021
- Abate by
- Jun 14, 2021
- Penalty
- Initial $6,827 · Current $5,500 Reduced
General-duty citation text
29 CFR 1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy: a) Guard shack - The receptacle near the electrical panel did not have a face plate, exposing employees to shock hazards, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $5500
- — C (S) $6827
- — Z (S) $6827
1910.303 B06
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $5,461 · Current $0 Reduced
General-duty citation text
29 CFR 1910.303(b)(6): Equipment located in damp or wet locations was not identified for that purpose. a) Guard shack - Under the bathroom sink, an orange extension cord was plugged into the receptacle and was not identified for damp or wet locations, exposing employees to shock hazards, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $5461
- — Z (S) $5461
1910.305 G01 IV A
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure: a) Gate K - The brown flexible cord was plugged in and powering the lysed light instead of utilizing fixed wiring, exposing employees to a shock hazard, on or about February 16, 2021. b) Gate J - The brown flexible cord was plugged in and powering the lysed light instead of utilizing fixed wiring, exposing employees to a shock hazard, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G01 IV B
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors: a) Guard shack - Flexible cords were run through walls, exposing employees to shock hazard, on or about February 16, 2021. b) Guard shack - In the restroom, flexible cords were run through walls and up through a vanity, exposing employees to shock hazard, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G01 IV D
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces: a) Guard shack - Above the entrance door frame, flexible cords and cables were attached to building surfaces, on or about February 16, 20201. b) Guard shack - Above the bathroom door, flexible cords and cables were attached to building surfaces, on or about February 16, 20201. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G01 IV E
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.305(g)(1)(iv)(E): Flexible cords and/or cables were concealed behind building walls, ceilings, or floors: a) Guard shack - Above the door frame, flexible cords and/or cables were concealed behind building walls, exposing employees to fire and shock hazards, on or about February 16, 2021. b) Guard shack - In the restroom, flexible cords and/or cables were concealed behind building walls, exposing employees to fire and shock hazards, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $0
- — C (S) $0
- — Z (S) $0
1910.305 G02 III
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $8,192 · Current $1,366 Reduced
General-duty citation text
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Guard Shack - In the bathroom, the power adapter cord was separating from the plug due to a lack of strain relief, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (O) $1366
- — C (S) $8192
- — Z (S) $8192
1910.305 J02 III
- Issued
- Jun 8, 2021
- Abate by
- Jun 18, 2021
- Penalty
- Initial $8,192 · Current $8,192
General-duty citation text
29 CFR 1910.305(j)(2)(iii):Nongrounding-type receptacles and connectors were used for grounding-type attachment plugs: a) Guard shack - The Lysed 10W light electrical cord was plugged into a non grounding type plug, which was connected too a non-grounding type extension cord, exposing employees to a shock hazard, on or about February 16, 2021. b) Guard shack - In the area of the desk, an electrical cord was plugged into a non grounding type plug, which was connected too a non-grounding type extension cord, exposing employees to shock hazard, on or about February 16, 2021. Abatement certification required.
Recent events (3)
- — J (S) $8192
- — C (S) $8192
- — Z (S) $8192
More inspections at A Pocono Country Place
View A Pocono Country Place's full OSHA safety record →
More inspections in this industry (NAICS 813990)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345153670.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.