Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: A POCONO COUNTRY PLACE

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of A POCONO COUNTRY PLACE in 112 COUNTRY PLACE DRIVE, TOBYHANNA, PA 18466 (NAICS 813990). OSHA activity number 345153670.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch A Pocono Country Place — free Get an email when a new federal OSHA severe-injury report for A Pocono Country Place is published. One employer, no account, unsubscribe in one click.
Site address
112 COUNTRY PLACE DRIVE
City
TOBYHANNA
State
PA
ZIP
18466
Mailing
112 COUNTRY PLACE DRIVE, TOBYHANNA, PA 18466
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
813990
Employees
75
Ownership type
A

14 citations on file for this inspection.

1910.147 C01

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Jun 8, 2021
Abate by
Jul 12, 2021
Penalty
Initial $9,557 · Current $0 Reduced
29 CFR  1910.147(c)(1): The employer did not establish a program consisting of an energy control procedure, employee training and periodic inspections to ensure that before any employee performed any servicing or maintenance on a machine or equipment where the unexpected energizing, startup or release of stored energy could occur and cause injury, the machine or equipment shall be isolated from the energy source and rendered inoperative:  a) K&L Gate - A lockout tagout program was not established for employees performing work on a lift gate and energy control devices were not applied,  exposing employees to live electrical, on or about February 16, 2021.  Abatement certification and documentation required.
Recent events (3)
  • — J (S) $0
  • — C (S) $9557
  • — Z (S) $9557

1910.303 B02

Deleted Serious Gravity 5 2 instances 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $5,461 · Current $0 Reduced
29 CFR 1910.303(b)(2): Listed or labeled equipment was not  installed and/or used in accordance with any instructions included in the listing or labeling:.  a) Guard shack - In the bathroom, across from the sink, a relocatable power tap were mounted to the walls, on or about February 16, 2021.   b) Guard shack - In the bathroom, adjacent to the sink, a relocatable power tap were mounted to the walls, on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $5461
  • — Z (S) $5461

1910.303 C03 I

Other-than-serious Gravity 5 2 instances 3 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $5,461 · Current $1,366 Reduced
29 CFR  1910.303(c)(3)(i): All splices and joints and the free ends of the conductors were not covered with an insulation equivalent to that of the conductors or with an insulating device identified for the purpose.  a) Guard shack - Above the door frame, the splices were not covered with insulation equivalent to that of the conductors, exposing employees to a shock hazard, on or about February 16, 2021.    b) Guard shack - In the bathroom,  the splices were not covered with insulation equivalent to that of the conductors, exposing employees to a shock hazard, on or about February 16, 2021.    c) Guard shack - In the bathroom, near the relocatable power tap, the splices were not covered with insulation equivalent to that of the conductors, exposing employees to a shock hazard, on or about February 16, 2021.    Abatement certification required.
Recent events (3)
  • — J (O) $1366
  • — C (S) $5461
  • — Z (S) $5461

1910.303 E01 II

Serious Gravity 1 3 instances 8 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $4,096 · Current $4,096
29 CFR  1910.303(e)(1)(ii): Electric equipment was used without markings giving voltage, current, wattage, or other ratings as necessary:  a) Guard shack - The breaker panel which controls the receptacles in the guard shack was not labeled,   on or about February 16, 2021.   b) Guard shack - The breaker panel, behind the entrance door, was not labeled,  on or about February 16, 2021.   c) Welcome Center - In the housekeeping closet, the breaker panels was not labeled,  on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (S) $4096
  • — C (S) $4096
  • — Z (S) $4096

1910.303 F

Serious Gravity 1 1 instance 2 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(f): Each service, feeder and branch circuit, at its disconnecting means or over current device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Guard shack - Inside the breaker panel, each service, feeder and branch circuit was not legibly marked to indicate its purpose, on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.303 G02 I

Other-than-serious Gravity 10 1 instance 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 14, 2021
Penalty
Initial $9,557 · Current $3,500 Reduced
29 CFR  1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, or by any of the following means identified in sub-paragraphs (A)through (D) of this paragraph:  a) Guard shack - In the bathroom, the continental access panel was open, exposing employees to electrocution hazard, on or about February 16, 2021.  Abatement certification and documentation required.
Recent events (3)
  • — J (O) $3500
  • — C (S) $9557
  • — Z (S) $9557

1910.305 B02 I

Serious Gravity 5 1 instance 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 14, 2021
Penalty
Initial $6,827 · Current $5,500 Reduced
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a) Guard shack - The receptacle near the electrical panel did not have a face plate, exposing employees to shock hazards, on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (S) $5500
  • — C (S) $6827
  • — Z (S) $6827

1910.303 B06

Deleted Serious Gravity 5 1 instance 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $5,461 · Current $0 Reduced
29 CFR  1910.303(b)(6): Equipment located in damp or wet locations was not identified for that purpose.  a) Guard shack - Under the bathroom sink, an orange extension cord was plugged into the receptacle and was not identified for damp or wet locations, exposing employees to shock hazards, on or about February 16, 2021.    Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $5461
  • — Z (S) $5461

1910.305 G01 IV A

Deleted Serious Gravity 5 2 instances 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(A): Flexible cords and/or cables were used as a substitute for the fixed wiring of a structure:  a) Gate K - The brown flexible cord was plugged in and powering the lysed light instead of utilizing fixed wiring, exposing employees to a shock hazard, on or about February 16, 2021.   b) Gate J - The brown flexible cord was plugged in and powering the lysed light instead of utilizing fixed wiring, exposing employees to a shock hazard, on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G01 IV B

Deleted Serious Gravity 5 2 instances 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(B): Flexible cords and/or cables were run through holes in walls, ceilings, or floors:    a) Guard shack - Flexible cords were run through walls, exposing employees to shock hazard, on or about February 16, 2021.   b) Guard shack - In the restroom, flexible cords were run through walls and up through a vanity, exposing employees to shock hazard, on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G01 IV D

Deleted Serious Gravity 5 2 instances 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(D): Flexible cords and cables were attached to building surfaces:  a) Guard shack - Above the entrance door frame, flexible cords and cables were attached to building surfaces, on or about February 16, 20201.   b) Guard shack - Above the bathroom door, flexible cords and cables were attached to building surfaces, on or about February 16, 20201.   Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G01 IV E

Deleted Serious Gravity 5 2 instances 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(1)(iv)(E): Flexible cords and/or cables were concealed behind building walls, ceilings, or floors:  a) Guard shack - Above the door frame, flexible cords and/or cables were concealed behind building walls, exposing employees to fire and shock hazards, on or about February 16, 2021.    b) Guard shack - In the restroom, flexible cords and/or cables were concealed behind building walls, exposing employees to fire and shock hazards, on or about February 16, 2021.    Abatement certification required.
Recent events (3)
  • — J (S) $0
  • — C (S) $0
  • — Z (S) $0

1910.305 G02 III

Other-than-serious Gravity 5 1 instance 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $8,192 · Current $1,366 Reduced
29 CFR  1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  a) Guard Shack - In the bathroom, the power adapter cord was separating from the plug due to a lack of strain relief, on or about February 16, 2021.   Abatement certification required.
Recent events (3)
  • — J (O) $1366
  • — C (S) $8192
  • — Z (S) $8192

1910.305 J02 III

Serious Gravity 5 2 instances 6 exposed
Issued
Jun 8, 2021
Abate by
Jun 18, 2021
Penalty
Initial $8,192 · Current $8,192
29 CFR  1910.305(j)(2)(iii):Nongrounding-type receptacles and connectors were used for grounding-type attachment plugs:  a) Guard shack - The Lysed 10W light electrical cord was plugged into a non grounding type plug, which was connected too a non-grounding type extension cord, exposing employees to a shock hazard, on or about February 16, 2021.    b) Guard shack -  In the area of the desk,  an electrical cord was plugged into a non grounding type plug, which was connected too a non-grounding type extension cord, exposing employees to shock hazard, on or about February 16, 2021.    Abatement certification required.
Recent events (3)
  • — J (S) $8192
  • — C (S) $8192
  • — Z (S) $8192

View A Pocono Country Place's full OSHA safety record →