BRECKENRIDGE, TX —
OSHA Inspection: J & J OILFIELD ELECTRIC CO., INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of J & J OILFIELD ELECTRIC CO., INC. in 566 FM 2231 EAST, BRECKENRIDGE, TX 76424 (NAICS 213112). OSHA activity number 345164057.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- J & J OILFIELD ELECTRIC CO., INC.
- Site address
- 566 FM 2231 EAST
- City
- BRECKENRIDGE
- State
- TX
- ZIP
- 76424
- Mailing
- 405 E. WALKER ST., BRECKENRIDGE, TX 76424
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213112
- Employees
- 38
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.132 D01
- Issued
- Mar 19, 2021
- Abate by
- Apr 16, 2021
- Penalty
- Initial $6,827 · Current $4,096 Reduced
General-duty citation text
29 CFR 1910.132(d)(1): The employer did not assess the workplace to determine if hazards are present, or are likely to be present, which necessitate the use of personal protective equipment (PPE): On or about February 23, 2021 and at times prior thereto, the employer did not assess the work place to determine if hazards were present and to determine the necessary PPE needed for safe work practices.
Recent events (2)
- — I (S) $4096.2
- — Z (S) $6827
1910.137 C02 VIII
- Issued
- Mar 19, 2021
- Abate by
- Apr 16, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.137(c)(2)(viii): Electrical protective equipment was not periodically electrical tested. Test voltages and the maximum intervals between tests will be in accordance with Table I-4 and Table I-5. On or about February 23, 2021, and at times prior thereto, the employer did not ensure that insulated electrical rubber gloves were tested every six months.
Recent events (2)
- — I (S) $0
- — Z (S) $0
1910.335 A01 I
- Issued
- Mar 19, 2021
- Abate by
- Apr 16, 2021
- Penalty
- Initial $9,557 · Current $5,734 Reduced
General-duty citation text
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards were not provided with, and did not use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to be performed. Note - Personal protective equipment requirements are contained in subpart I of this part On or about February 23, 2021 and at times prior thereto, and at times thereafter, the employer did not ensure employees were provided and wore electrical personal protective equipment when opening and conducting voltage readings on an energized 2300 volt electrical cabinet, exposing employees to arc flash hazards.
Recent events (2)
- — I (S) $5734.2
- — Z (S) $9557
1904.39 A02
- Issued
- Mar 19, 2021
- Abate by
- Apr 16, 2021
- Penalty
- Initial $1,000 · Current $600 Reduced
General-duty citation text
29 CFR 1904.39(a)(2): The employer did not report within 24-hours a work-related incident resulting in in-patient hospitalization, amputation or the loss of an eye: The employer did not report an electrical arch flash incident that occurred on or about February 20, 2021, at 566 FM 2231 East, Breckenridge TX 76424 within the required 24 hours after knowing of the hospitalization. The injury was reported on February 22, 2021.
Recent events (2)
- — I (O) $600
- — Z (O) $1000
More inspections in this industry (NAICS 213112)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345164057.