Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: ELITE POWER & RECOVERY, INC.

Federal Agency inspection · Safety discipline

On , OSHA opened a federal Agency safety inspection of ELITE POWER & RECOVERY, INC. in 1000 SOUTHSIDE RD., EL PASO, TX 79927 (NAICS 221122). OSHA activity number 345164537.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Elite Power & Recovery, INC. — free Get an email when a new federal OSHA severe-injury report for Elite Power & Recovery, INC. is published. One employer, no account, unsubscribe in one click.
Site address
1000 SOUTHSIDE RD.
City
EL PASO
State
TX
ZIP
79927
Mailing
2121 OSUNA ROAD NORTHEAST, ALBUQUERQUE, NM 87113
Inspection type
Federal Agency (M)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
34
Ownership type
A

3 citations on file for this inspection.

1910.67 C02 I

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Aug 23, 2021
Abate by
Oct 15, 2021
Penalty
Initial $9,557 · Current $6,000 Reduced
29 CFR  1910.67(c)(2)(i): Lift controls were not tested each day prior to use to determine that such controls were in safe working condition.  On or about February 25, 2021, an employee used an articulating boom without first testing the controls to determine if they were in safe working condition.
Recent events (2)
  • — I (O) $6000
  • — Z (S) $9557

1910.269 L05 II

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Aug 23, 2021
Abate by
Oct 15, 2021
Penalty
Initial $9,557 · Current $6,000 Reduced
29 CFR  1910.269(l)(5)(ii): The unprotected employee did not position or work outside the minimum approach distance as required.   On or about February 25, an employee, while not wearing protective gloves and was not being protected with insulating equipment covering the energized power line, did not position himself outside the minimum approach distance as required.
Recent events (2)
  • — I (O) $6000
  • — Z (S) $9557

1910.335 A02 II

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Aug 23, 2021
Abate by
Oct 15, 2021
Penalty
Initial $9,557 · Current $6,000 Reduced
29 CFR  1910.335(a)(2)(ii):Protective shields, protective barriers, or insulating materials were not used to protect each employee from shock, burns, or other electrically related injuries while that employee was working near exposed energized parts:  On or about February 25, 2021, an employee was working near an energized power line.  The power line was not protected to keep the employee from making contact.  The employee was exposed to the hazard of electrical shock.
Recent events (2)
  • — I (O) $6000
  • — Z (S) $9557