Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: SUNNY DELIGHT BEVERAGES CO.

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of SUNNY DELIGHT BEVERAGES CO. in 7050 LAGRANGE BLVD, ATLANTA, GA 30336 (NAICS 311411). OSHA activity number 345167639.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sunny Delight Beverages CO. — free Get an email when a new federal OSHA severe-injury report for Sunny Delight Beverages CO. is published. One employer, no account, unsubscribe in one click.
Site address
7050 LAGRANGE BLVD
City
ATLANTA
State
GA
ZIP
30336
Mailing
1 HIGH RIDGE PARK 3RD FLOOR, STAMFORD, CT 06905
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
311411
Employees
100
Ownership type
A

3 citations on file for this inspection.

1910.178 Q01

Serious Gravity 5 1 instance 3 exposed
Issued
Jun 11, 2021
Penalty
Initial $5,969 · Current $5,969
29 CFR  1910.178(q)(1):Any power-operated industrial truck not in safe operating condition was not taken out of service, and/or repairs were not made by authorized personnel:  (a) Shipping Department: On or about 2/17/2021 and at times prior, the employer exposed powered industrial truck operators who transport material throughout the facility to electrical hazards in that battery cables on the #20 Caterpillar powered industrial truck had exposed wiring and was not taken out of service.
Recent events (1)
  • — Z (S) $5969

1910.303 G02 II

Serious Gravity 5 1 instance 2 exposed
Issued
Jun 11, 2021
Penalty
Initial $5,969 · Current $5,969
29 CFR  1910.303(g)(2)(ii): In locations where electric equipment was likely to be exposed to physical damage, enclosures or guards were not so arranged and of such strength as to prevent such damage:   (a) Receiving Department - Battery Charging Area : On or about 2/17/2021 and at times prior, the employer exposed forklift operators to electrical hazards in that the battery charging socket connector was damaged and the battery cable was pulled out with exposed wiring.
Recent events (1)
  • — Z (S) $5969

1910.305 G02 III

Other-than-serious 1 instance 2 exposed
Issued
Jun 11, 2021
Abate by
Jul 7, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(2)(iii):Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws:  (a)Receiving Department Battery Charging Area: On or about 2/17/2021, and at times prior, the employer exposed powered industrial truck operators to electrical hazards, in that the plug-in cable for the Green Diamond battery charger did not have strain relief to prevent tension to the terminal screws.
Recent events (1)
  • — Z (O) $0

View Sunny Delight Beverages CO.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345167639.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.