Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: VIA AQUARIUM

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of VIA AQUARIUM in 93 W. CAMPBELL RD, SCHENECTADY, NY 12306 (NAICS 712130). OSHA activity number 345216634.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch VIA Aquarium — free Get an email when a new federal OSHA severe-injury report for VIA Aquarium is published. One employer, no account, unsubscribe in one click.
Establishment
VIA AQUARIUM
Site address
93 W. CAMPBELL RD
City
SCHENECTADY
State
NY
ZIP
12306
Mailing
93 W. CAMPBELL RD, SCHENECTADY, NY 12306
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
712130
Employees
25
Ownership type
A

5 citations on file for this inspection.

1910.29 B01

Serious Gravity 5 1 instance 10 exposed
Issued
Jun 17, 2021
Abate by
Aug 4, 2021
Penalty
Initial $3,901 · Current $2,536 Reduced
29 CFR 1910.29(b)(1): The employer did not ensure that  guardrail systems met the requirement that the top edge height of top rails, or equivalent guardrail system members, that are 42 inches (107 cm), plus or minus 3 inches (8 cm), above the walking-working surface. The top edge height may exceed 45 inches (114 cm), provided the guardrail system meets all other criteria of paragraph (b) of this section (see Figure D11 of this section).  a) 93 W. Campbell Road, Schenectady, NY- On or about March 19, 2021, employees were utilizing a work platform with a guardrail top rail approximately 27 inches above the walking-working surface, exposing the employees to a  fall hazard of approximately of seven (7) feet.
Recent events (2)
  • — I (S) $2535.65
  • — Z (S) $3901

1910.303 B02

Serious Gravity 5 10 instances 25 exposed
Issued
Jun 17, 2021
Abate by
Aug 4, 2021
Penalty
Initial $3,121 · Current $2,029 Reduced
29 CFR  1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) 93 W. Campbell Road, Schenectady, NY- On or about  and times prior to March 19, 2021, the employer used multiple temporary power strips and extension cords interconnected together as a permanent wiring source, exposing employees to second degree burns.
Recent events (2)
  • — I (S) $2028.65
  • — Z (S) $3121

1910.305 J02 IV

Serious Gravity 5 20 instances 10 exposed
Issued
Jun 17, 2021
Abate by
Aug 4, 2021
Penalty
Initial $3,121 · Current $2,029 Reduced
29 CFR  1910.305(j)(2)(iv): Receptacles installed in a wet or damp location were not suitable for the location:  a) 93 W. Campbell Road, Schenectady, NY- On or about March 19, 2021, employees were exposed to an electrocution hazard while maintaining aquariums and related equipment that were connected to electric receptacles that were not suitable for the wet work environment .
Recent events (2)
  • — I (S) $2028.65
  • — Z (S) $3121

1910.304 B03 II A

Serious Gravity 5 10 instances 10 exposed
Issued
Jun 17, 2021
Abate by
Aug 4, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.304(b)(3)(ii)(A):All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that are not part of the permanent wiring of the building or structure and that are in use by personnel did not have ground-fault circuit-interrupter protection for personnel.  a) 93 W. Campbell Road, Schenectady, NY- On or about March 19, 2021, employees were exposed to potential injury while working with extension cords and power strips near water sources to energize aquariums and accessories without the use of GFCI protection.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 A02 I

Serious Gravity 5 12 instances 25 exposed
Issued
Jun 17, 2021
Abate by
Aug 4, 2021
Penalty
Initial $3,121 · Current $2,029 Reduced
29 CFR  1910.305(a)(2)(i): Temporary electrical power and lighting installation(s) 600 volts, nominal, or less were used in prohibited manners:Note:  Temporary electrical power and lighting installation(s) may only be used as specified by 1910.305(a)(2)(i)(A) through 1910.305(a)(2)(i)(C).   a) 93 W. Campbell Road, Schenectady, NY- On or about March 19, 2021, the employer was using temporary power in the form of extension cords as a permanent power source to energize aquariums, exposing employees to a shock or burn hazard.
Recent events (2)
  • — I (S) $2028.65
  • — Z (S) $3121

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345216634.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.