OSHA Inspection: MIDWAY INDUSTRIAL SUPPLY, INC.

Planned inspection · Health discipline

On , OSHA opened a planned health inspection of MIDWAY INDUSTRIAL SUPPLY, INC. in 51 WURZ AVENUE, UTICA, NY 13502 (NAICS 423840). OSHA activity number 345265367.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Midway Industrial Supply, INC. — free Get an email when a new federal OSHA severe-injury report for Midway Industrial Supply, INC. is published. One employer, no account, unsubscribe in one click.
Site address
51 WURZ AVENUE
City
UTICA
State
NY
ZIP
13502
Mailing
51 WURZ AVENUE, UTICA, NY 13502
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Health
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
423840
Employees
30
Ownership type
A

7 citations on file for this inspection.

1910.212 A01

Serious Gravity 1 2 instances 2 exposed
Issued
Oct 7, 2021
Penalty
Initial $3,481 · Current $2,611 Reduced
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created point of operation, rotating parts, and flying chips:  a) Machine Shop, on or about 5/6/2021:  Bridgeport Milling Machine was not provided with a chuck and tool guard.  b) Machine Shop, on or about 5/6/2021:  Jet Geared Head Precision Lathe Model No. GH-1880ZX the rotating chuck was not guarded.
Recent events (2)
  • — I (S) $2610.75
  • — Z (S) $3481

1910.215 B09

Serious Gravity 1 1 instance 2 exposed
Issued
Oct 7, 2021
Penalty
Initial $3,481 · Current $2,611 Reduced
29 CFR 1910.215(b)(9):  The distance between the abrasive wheel periphery(s) and the adjustable tongue or the end of the safety guard peripheral member at the top exceeded one fourth inch:    a)  Machine Shop, on or about 5/6/2021:  A Cincinnati Bench Grinder had an opening between the tongue guard and grinding wheel that measured 2-inches at the left wheel and 1/2-inch at the right wheel.
Recent events (2)
  • — I (S) $2610.75
  • — Z (S) $3481

1910.303 G02 I

Other-than-serious Gravity 1 2 instances 2 exposed
Issued
Oct 7, 2021
Penalty
Initial $3,481 · Current $2,611 Reduced
29 CFR  1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating  at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i):  a) Machine Shop Area, on or about 5/6/21:  A 120/240 breaker panel box had the entire cover missing on the breaker panel box.  b) Machine Shop Area, on or about 5/6/21: A 120/240 volt breaker panel box labeled MDP had three blanks missing.
Recent events (2)
  • — I (O) $2610.75
  • — Z (S) $3481

1910.304 F01 IV

Other-than-serious Gravity 1 1 instance 3 exposed
Issued
Oct 7, 2021
Penalty
Initial $3,481 · Current $2,611 Reduced
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less were not readily accessible to each employee or authorized building management personnel:  a) Warehouse Shop Area, on or about 5/6/2021: Access to a Breaker Panel Box controlling equipment in the Hose Room was blocked by a shelving unit stored right up against the Breaker Panel Box.
Recent events (2)
  • — I (O) $2610.75
  • — Z (S) $3481

1910.304 G05

Other-than-serious Gravity 1 1 instance 3 exposed
Issued
Oct 7, 2021
Penalty
Initial $0 · Current $0
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous and effective:   a)  Hose Room, on or about 5/6/2021: Bronco AC Warner Electric Machine had ground pin missing from plug end.
Recent events (2)
  • — I (O) $0
  • — Z (S) $0

1910.37 B02

Other-than-serious 1 instance 3 exposed
Issued
Oct 7, 2021
Penalty
Initial $0 · Current $0
29 CFR 1910.37(b)(2): Each exit was not clearly visible and marked by a sign reading "EXIT":  a) Shop Area, on or about 5/6/021: The West Warehouse exit door leading to the outside was not marked.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.219 E02 I

Other-than-serious 1 instance 2 exposed
Issued
Oct 7, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.219(e)(2)(i):Overhead horizontal belt(s) with lower parts seven -7 feet or less from the floor(s) or platform(s) were not guarded on the sides and bottom in accordance with the requirements specified at CFR 1910.219(o)(3)(a):  a) Machine Shop, on or about 5/6/21:  Bridgeport Milling Machine did not have the overhead horizontal belt guarded on the sides.  The opening at the horizontal belt was 9" x 3", 6.5' from the ground.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Midway Industrial Supply, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345265367.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.