OSHA Inspection: THE HOME DEPOT #0457

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of THE HOME DEPOT #0457 in 9170 E. TALKING STICK WAY, SCOTTSDALE, AZ 85250 (NAICS 444110). OSHA activity number 345304679.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Home Depot #0457 — free Get an email when a new federal OSHA severe-injury report for The Home Depot #0457 is published. One employer, no account, unsubscribe in one click.
Site address
9170 E. TALKING STICK WAY
City
SCOTTSDALE
State
AZ
ZIP
85250
Mailing
9170 E. TALKING STICK WAY, SCOTTSDALE, AZ 85250
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
444110
Employees
150
Ownership type
A

5 citations on file for this inspection.

1910.303 B02

Serious Gravity 1 5 instances 20 exposed
Issued
Jul 9, 2021
Penalty
Initial $5,851 · Current $5,851
29 CFR  1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling:  a) CUSTOMER SERVICE DESK: Employees were exposed to fire and electrical hazards where a relocatable power tap was used to charge three Mart Cart mobile scooters. b) BREAKROOM: Employees were exposed to fire and electrical hazards where a three-way splitter was used to power a microwave and popcorn machine. c) BREAKROOM: Employees were exposed to fire and electrical hazards where a six-way splitter was used to power two Keurig coffee machines and one toaster.  d) COMPUTER ROOM: Employees were exposed to fire and electrical hazards where a relocatable power tap was connected in series (daisy chained) with a two-way splitter to power two Lexmark copy/scan/fax machines.  e) OFFICE HALLWAY: Employees were exposed to fire and electrical hazards where a relocatable power tap was used to charge three batteries for power tools and chargers to handheld phone/radios.
Recent events (1)
  • — Z (S) $5851

1910.37 B06

Other-than-serious 11 instances 150 exposed
Issued
Jul 9, 2021
Abate by
Aug 4, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.37(b)(6):Each exit sign was not illuminated to a surface value of at least five foot-candles (54 lux) by a reliable light source and be distinctive in color:  a) CUSTOMER SERVICE DESK: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  b) ASDS OFFICE: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  c) ELECTRICAL DEPARTEMENT: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  d) GARDEN CENTER: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  e) EXIT DOOR #2: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  f) EXIT DOOR #3: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  g) EXIT DOOR #6: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  h) EXIT DOOR #7: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  i) EXIT DOOR #8: Exit sign above the exit was not illuminated, exposing employees to fire hazards.  j) CUSTOMER CHECKOUT: East exit sign above the exit was not illuminated, exposing employees to fire hazards.  k) CUSTOMER CHECKOUT: West exit sign above the exit was not illuminated, exposing employees to fire hazards.
Recent events (1)
  • — Z (O) $0

1910.157 C01

Other-than-serious 7 instances 150 exposed
Issued
Jul 9, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.157(c)(1):Portable fire extinguishers were not mounted, located and identified so that they were readily accessible without subjecting the employees to injuries:  a) BREAKROOM: The fire extinguisher was not mounted nor a sign installed to identify its location, exposing employees to fire hazards.  b) COMPUTER ROOM: The fire extinguisher was not mounted nor signs installed to identify its location, exposing employees to fire hazards.  c) ISLE 39: Where a fire extinguisher was mounted, a sign was not installed to identify its location, exposing employees to fire hazards.  d) ISLE 45: Where a fire extinguisher was mounted, a sign was not installed to identify its location, exposing employees to fire hazards.  e) ISLE 59: Where a fire extinguisher was mounted, a sign was not installed to identify its location, exposing employees to fire hazards.  f) ISLE 60: Where a fire extinguisher was mounted, a sign was not installed to identify its location, exposing employees to fire hazards.  g) ISLE 67:Where a fire extinguisher was mounted, a sign was not installed to identify its location, exposing employees to fire hazards.
Recent events (1)
  • — Z (O) $0

1910.213 S06

Other-than-serious 1 instance 5 exposed
Issued
Jul 9, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.213(s)(6): Cleanliness around working machinery was not maintained to prevent fire hazards and ensure the effective functioning of guards:  LUMBER DEPARTMENT: An accumulation of wood dust around the motor of the Kufo Seco Dust Collector exposed employees to fire hazards.
Recent events (1)
  • — Z (O) $0

1910.303 G01 II

Other-than-serious 1 instance 2 exposed
Issued
Jul 9, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(g)(1)(ii):The required working space about electric equipment rated 600 volts, nominal, or less to ground, was used for storage:  a) COMPUTER ROOM: Two electrical panels were blocked, exposing employees to electrical and fire hazards.
Recent events (1)
  • — Z (O) $0

View The Home Depot #0457's full OSHA safety record →