Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: DUKE ENERGY

Complaint inspection · Safety discipline

On , OSHA opened a complaint safety inspection of DUKE ENERGY in 593 TODHUNTER RD., MONROE, OH 45050 (NAICS 811118). OSHA activity number 345312979.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Duke Energy — free Get an email when a new federal OSHA severe-injury report for Duke Energy is published. One employer, no account, unsubscribe in one click.
Establishment
DUKE ENERGY
Site address
593 TODHUNTER RD.
City
MONROE
State
OH
ZIP
45050
Mailing
593 TODHUNTER RD., MONROE, OH 45050
Inspection type
Complaint (B)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
811118
Employees
150
Ownership type
A

6 citations on file for this inspection.

1910.304 G05

Deleted Serious Gravity 10 1 instance 10 exposed
Issued
Oct 1, 2021
Abate by
Oct 28, 2021
Penalty
Initial $13,653 · Current $0 Reduced
29 CFR  1910.304(g)(5):Grounding path. The path to ground from circuits, equipment, and enclosures shall be permanent, continuous, and effective.  a)  On or before 4/28/2021,  the employer did not ensure path to ground was maintained when employees were spraying water around the testing tank to prevent employees from being shocked,  the energized on/off switch for the testing tank is plugged behind the tank into an extension cord that is plugged into a wall 110v outlet.
Recent events (2)
  • — I (S) $0
  • — Z (S) $13653

1910.305 E02

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 1, 2021
Abate by
Nov 19, 2021
Penalty
Initial $13,653 · Current $8,000 Reduced
29 CFR  1910.305(e)(2):Switches, circuit breakers, and switchboards. Switches, circuit breakers, and switchboards installed in wet locations shall be enclosed in weatherproof enclosures.  a)  On or before 4/28/2021, the employer did not ensure that the on/off switch was enclosed in a weatherproof enclosure on a testing tank filled with approximately 580 gallons of water and where employees spray water around the tank to clean up oil spills.
Recent events (2)
  • — I (S) $8000
  • — Z (S) $13653

1910.334 A04

Serious Gravity 10 1 instance 1 exposed
Issued
Oct 1, 2021
Abate by
Nov 19, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.334(a)(4):Conductive work locations. Portable electric equipment and flexible cords used in highly conductive work locations (such a those inundated with water or other conductive liquids), or in job locations where employees are likely to contact water or conductive liquids ,shall be approved for those locations.  a)  On or before 4/28/2021 the employer did not ensure that the extension cord plugged into the on/off switch  was intended for wet locations. Employees were exposed to a shock hazard due to the energized  electrical cord located behind the testing tank being saturated with water while cleaning oil spills.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G01 I

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Oct 1, 2021
Abate by
Nov 19, 2021
Penalty
Initial $13,653 · Current $0 Reduced
29 CFR  1910.305(g)(1)(i): Flexible cords and cables shall be approved for conditions of use and location.  a)  On or before 4/28/2021,  the employer did not ensure that the flexible cord attached to the on/off  switch that was plugged into the extension cord that was plugged into the outlet that was being used to run power to a homemade test tank with approximately 580 gallons of water was approved for use as temporary wiring.  Employees were exposed to a shock hazard due to a flexible cord being used to run the electrical on/off switch being sprayed with water.
Recent events (2)
  • — I (O) $0
  • — Z (S) $13653

1910.145 C02

Other-than-serious 1 instance 2 exposed
Issued
Oct 1, 2021
Abate by
Oct 21, 2021
Penalty
Initial $1,205 · Current $700 Reduced
29 CFR  1910.145(c)(2): Caution signs.  (i)  Caution signs shall be used only to warn against potential hazards or to caution against unsafe practices.   (ii)  All employees shall be instructed that caution signs indicate a possible hazard against which proper precaution should be taken.   a)  On or before 4/28/2021,  the employer did not provide a caution sign to warn employees of the potential for injury of burns from to the copper hot water  line set above 120 degrees attached to the garden hose that employees utilized for cleaning around the testing tank.
Recent events (2)
  • — I (O) $700
  • — Z (O) $1205

1910.335 B01

Deleted Other-than-serious 1 instance 1 exposed
Issued
Oct 1, 2021
Abate by
Nov 19, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.335(b)(1):Safety signs and tags. Safety signs, safety symbols, or accident prevention tags shall be used where necessary to warn employees about electrical hazards which may endanger them, as required by 1910.145.  a) On or about 4/28/2021 the employer did not ensure that safety signs were in place to warn employees of the electrical testing of the bucket truck liners.  Employees were exposed to 100,000 volts of electricity during the testing of the bucket truck liners.