CHEEKTOWAGA, NY —
OSHA Inspection: ICAD SERVICES, INC
Unprogrammed Other inspection · Safety discipline
At a glance
On , OSHA opened an unprogrammed Other safety inspection of ICAD SERVICES, INC in 135 BUELL AVENUE, CHEEKTOWAGA, NY 14225 (NAICS 236220). OSHA activity number 345322598.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- ICAD SERVICES, INC
- Site address
- 135 BUELL AVENUE
- City
- CHEEKTOWAGA
- State
- NY
- ZIP
- 14225
- Mailing
- 4 MILL RIDGE LANE SUITE 10, CHESTER, NJ 07930
What kind of inspection was it?
- Inspection type
- Unprogrammed Other (I)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 236220
- Employees
- 2
- Ownership type
- A
Citations
3 citations on file for this inspection.
1926.405 B01
- Issued
- Aug 12, 2021
- Penalty
- Initial $1,691 · Current $1,691
General-duty citation text
29 CFR 1926.405(b)(1):Unused openings in cabinets, boxes, and fittings were not effectively closed: a) On or about 5/19/2021, at the building area of the site, Cheektowaga, NY. Temporary panel , of 480-Volt and 250-Amp, lacked 16 blanks to effectively close unused openings. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (S) $1691
1926.403 G
- Issued
- Aug 12, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(g):Electrical equipment which was used did not have other markings giving voltage, current, wattage, or other ratings as necessary: a) On or about 5/19/2021, at the building area of the site, Cheektowaga, NY. Temporary panel, 480-Volt/250-Amp, was used and it did not have the markings giving voltage, current, wattage, or other ratings. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
1926.403 H
- Issued
- Aug 12, 2021
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1926.403(h):Each service, feeder, and branch circuit was not legibly marked at its disconnecting means or overcurrent device to indicate its purpose, nor located and arranged so that the purpose was evident: a) On or about 5/19/2021, at the building area of the site, Cheektowaga, NY. Temporary panel, 480-Volt/250-Amp, lacked the directory to indicate the purpose of overcurrent devices. NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
- — Z (O) $0
More inspections in this industry (NAICS 236220)
More inspections in NY
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345322598.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.