OSHA Inspection: TOLEDO MUDLOGGING SERVICES, INC.

Unprogrammed Other inspection · Safety discipline

On , OSHA opened an unprogrammed Other safety inspection of TOLEDO MUDLOGGING SERVICES, INC. in TINIAN- PREWIT 24-14 UNIT WELL NO 321H 9.6 MILES SW DIRECTION FROM PECOS, PECOS, TX 79772 (NAICS 213112). OSHA activity number 345347926.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Toledo Mudlogging Services, INC. — free Get an email when a new federal OSHA severe-injury report for Toledo Mudlogging Services, INC. is published. One employer, no account, unsubscribe in one click.
Site address
TINIAN- PREWIT 24-14 UNIT WELL NO 321H 9.6 MILES SW DIRECTION FROM PECOS
City
PECOS
State
TX
ZIP
79772
Mailing
5530 MARTHAVILLE RD, MANY, LA 71449
Inspection type
Unprogrammed Other (I)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
213112
Employees
2
Ownership type
A

3 citations on file for this inspection.

1910.304 B04 II B

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 19, 2021
Abate by
Sep 8, 2021
Penalty
Initial $5,969 · Current $3,000 Reduced
29 CFR 1910.304(b)(4)(ii)(B):Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle supplied a total cord- and plug-connected load in excess of the maximum specified in Table S-4.  On or about April 07, 2021 a receptacle connected to a branch circuit supplying two or more receptacles were being used to power a two lamp system and two pancake compressors that exceeded the total cord and plug connected load of 12 Amperes as specified in Table S-4. This condition exposed employees to fire and electrical hazards.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5969

1910.305 G01 IV C

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 19, 2021
Abate by
Sep 8, 2021
Penalty
Initial $5,969 · Current $3,000 Reduced
29 CFR  1910.305(g)(1)(iv)(C): Unless specifically permitted otherwise in paragraph (g)(1)(ii) of this section, flexible cords and cables may not be used where run through doorways, windows, or similar openings;   On or about April 07, 2021 a flexible cord was ran through a doorway to power a receptacle where an outlet strip and heat lamp were connected. This condition exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $3000
  • — Z (S) $5969

1910.305 J01 I

Serious Gravity 5 1 instance 2 exposed
Issued
Aug 19, 2021
Abate by
Sep 8, 2021
Penalty
Initial $8,953 · Current $4,000 Reduced
29 CFR  1910.305(j)(1)(i):Fixtures, lampholders, lamps, rosettes, and receptacles located had live parts normally exposed to employee contact:  On or about April 07, 2021 a heat lamp with exposed live wires was used by employees.  This condition exposed employees to electrical shock hazards.
Recent events (2)
  • — I (S) $4000
  • — Z (S) $8953

View Toledo Mudlogging Services, INC.'s full OSHA safety record →