Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: OG&E ENERGY CORP.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of OG&E ENERGY CORP. in 2219 DAWN MARIE DRIVE, OKLAHOMA CITY, OK 73112 (NAICS 221122). OSHA activity number 345367973.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch OG&E Energy Corp. — free Get an email when a new federal OSHA severe-injury report for OG&E Energy Corp. is published. One employer, no account, unsubscribe in one click.
Establishment
OG&E ENERGY CORP.
Site address
2219 DAWN MARIE DRIVE
City
OKLAHOMA CITY
State
OK
ZIP
73112
Mailing
PO BOX 321 MAILCODE 506, OKLAHOMA CITY, OK 73101
Inspection type
Referral (C)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
221122
Employees
250
Ownership type
A

3 citations on file for this inspection.

1910.269 C02

Deleted Serious Gravity 5 1 instance 4 exposed
Issued
Dec 7, 2021
Abate by
Dec 21, 2021
Penalty
Initial $10,533 · Current $0 Reduced
29 CFR  1910.269(c)(2):  The job briefing did not cover at least the following subjects:  hazards associated with the job, work procedures involved, special precautions, energy-source controls, and personal protective equipment requirements.  On or about June, 12, 2021, the employer did not conduct a job briefing that included, but was not limited to energy-source controls before performing maintenance on a down power line. This exposed the employees to electrical hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $10533
  • — Z (S) $10533

1910.269 L01 III

Other-than-serious Gravity 10 1 instance 4 exposed
Issued
Dec 7, 2021
Abate by
Apr 13, 2023
Penalty
Initial $12,288 · Current $2,000 Reduced
29 CFR  1910.269(l)(1)(iii):  Electric lines and equipment were not considered and treated as energized before they had been deenergized in accordance with paragraph (d) or (m) of this section.  On or about June 12, 2021, the employer did not  ensure all electric lines were treated as energized and did not verify if the lines were deenergized before work began. This exposed the employees to electrical hazards.
Recent events (3)
  • — F (O) $2000
  • — C (S) $12288
  • — Z (S) $12288

1910.269 L05 II

Deleted Serious Gravity 10 1 instance 2 exposed
Issued
Dec 7, 2021
Abate by
Dec 21, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.269(l)(5)(ii):  When an employee performs work near exposed parts energized at more than 600 volts, but not more than 72.5 kilovolts, and is not wearing rubber insulating gloves, being protected by insulating equipment covering the energized parts, performing work using live-line tools, or performing live-line bare hand work under paragraph (q)(3) of this section, the unprotected employee did not work from a position where he or she cannot reach into the minimum approach distance, established by the employer under paragraph (l)(3)(i) of this section.   On or about June ,  12, 2021, the employer did not ensure employees, repairing down powerlines near energized lines, positioned or worked outside of the minimum approach distance. This exposed the employees to electrical hazards.
Recent events (3)
  • — F (S) $0
  • — C (S) $0
  • — Z (S) $0

View OG&E Energy Corp.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345367973.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.