OSHA Inspection: NEW RIVER ELECTRICAL CORPORATION

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of NEW RIVER ELECTRICAL CORPORATION in ROW NEAR 16TH STREET AND MILL STREET, COSHOCTON, OH 43812 (NAICS 238210). OSHA activity number 345414916.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch NEW River Electrical Corporation — free Get an email when a new federal OSHA severe-injury report for NEW River Electrical Corporation is published. One employer, no account, unsubscribe in one click.
Site address
ROW NEAR 16TH STREET AND MILL STREET
City
COSHOCTON
State
OH
ZIP
43812
Mailing
15 CLOVERDALE PLACE, CLOVERDALE, VA 24077
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
A
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238210
Employees
750
Ownership type
A

3 citations on file for this inspection.

1926.959 D01

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 13, 2021
Abate by
Jun 16, 2022
Penalty
Initial $13,653 · Current $13,653
29 CFR  1926.959(d)(1):Minimum approach distance. Mechanical equipment shall be operated so that the minimum approach distances, established by the employer under � 1926.960(c)(1)(i), are maintained from exposed energized lines and equipment. However, the insulated portion of an aerial lift operated by a qualified employee in the lift is exempt from this requirement if the applicable minimum approach distance is maintained between the uninsulated portions of the aerial lift and exposed objects having a different electrical potential.  a. On or before July 6, 2021 at a right of way located near 16th St. and Mill Street in Coshocton Ohio where employees were using a digger derrick to load previously removed wooden electrical poles onto a trailer for removal from the worksite, the boom of the digger derrick was operated within the minimum approach distance of a 34.5kV overhead electrical line, resulting in the hospitalization of an employee due to the resulting electrical shock.
Recent events (3)
  • — J (S) $13653
  • — C (S) $13653
  • — Z (S) $13653

1926.959 D03

Serious Gravity 10 1 instance 2 exposed
Issued
Oct 13, 2021
Abate by
Jun 16, 2022
Penalty
Initial $13,653 · Current $0 Reduced
29 CFR  1926.959(d)(3):Extra precautions. If, during operation of the mechanical equipment, that equipment could become energized, the operation also shall comply with at least one of paragraphs (d)(3)(i) through (d)(3)(iii) of this section.  a. On or before July 6, 2021 at a right of way located near 16th St. and Mill Street in Coshocton Ohio where employees were using a digger derrick to load previously removed wooden electrical poles onto a trailer for removal from the worksite, extra precautions were not taken to prevent the digger derrick from becoming energized while the boom of the digger derrick was operated under a 34.5kV overhead electrical line, resulting in the hospitalization of an employee due to the resulting electrical shock.
Recent events (3)
  • — J (S) $0
  • — C (S) $13653
  • — Z (S) $13653

1926.959 D02

Other-than-serious Gravity 10 1 instance 2 exposed
Issued
Oct 13, 2021
Abate by
Jun 16, 2022
Penalty
Initial $13,653 · Current $13,653
29 CFR  1926.959(d)(2):Observer. A designated employee other than the equipment operator shall observe the approach distance to exposed lines and equipment and provide timely warnings before the minimum approach distance required by paragraph (d)(1) of this section is reached, unless the employer can demonstrate that the operator can accurately determine that the minimum approach distance is being maintained.  a. On or before July 6, 2021 at a right of way located near 16th St. and Mill Street in Coshocton Ohio where employees were using a digger derrick to load previously removed wooden electrical poles onto a trailer for removal from the worksite, an employee was not designated to observed the approach distance of the boom and the energized overhead lines when the boom came into contact with the lines, resulting in the hospitalization of an employee due to the resulting electrical shock.
Recent events (3)
  • — J (O) $13653
  • — C (S) $13653
  • — Z (S) $13653

View NEW River Electrical Corporation's full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345414916.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.