OSHA Inspection: SYSCO WEST COAST FLORIDA, INC.

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of SYSCO WEST COAST FLORIDA, INC. in 3000 69TH STREET EAST, PALMETTO, FL 34221 (NAICS 424410). OSHA activity number 345432090.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Sysco West Coast Florida, INC. — free Get an email when a new federal OSHA severe-injury report for Sysco West Coast Florida, INC. is published. One employer, no account, unsubscribe in one click.
Site address
3000 69TH STREET EAST
City
PALMETTO
State
FL
ZIP
34221
Mailing
P.O. BOX 1911, PALMETTO, FL 34220
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
424410
Employees
500
Ownership type
A

4 citations on file for this inspection.

1910.147 C04 I

Serious Gravity 5 1 instance 6 exposed
Issued
Dec 15, 2021
Abate by
Feb 28, 2022
Penalty
Initial $9,753 · Current $8,778 Reduced
29 CFR  1910.147(c)(4)(i):Procedures were not developed, documented and utilized for the control of potentially hazardous energy when employees were engaged in activities covered by this section:  For employees working at the Sysco building  in Palmetto Florida, procedures to control kinetic energy were not developed when authorized employees were removing and replacing the drive belts on the two cooling tower fans. The fans were spun by a single motor mounted between the fan assemblies. Fan continued to move after the main electrical source had been turned off creating an amputation hazard between the belts and the pulley, on or about July 12, 2021.
Recent events (2)
  • — I (S) $8777.7
  • — Z (S) $9753

1910.147 D05 I

Serious Gravity 5 1 instance 6 exposed
Issued
Dec 15, 2021
Abate by
Feb 28, 2022
Penalty
Initial $0 · Current $0
29 CFR  1910.147(d)(5)(i): All potentially hazardous stored or residual energy was not relieved, disconnected, restrained or otherwise rendered safe after the application of lockout or tagout devices to energy isolating devices:   For employees working at the Sysco building  in Palmetto Florida ,  employees were removing and replacing the drive belts on the two cooling tower fans when the kinetic energy was not isolated. The fans were spun by a single motor mounted between the fan assemblies. When one belt is removed from the pulley, the second fan still had the ability to continue move.  This action creates an amputation hazard between the belts and the pulley, on or about July 12, 2021.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C06 I A

Serious Gravity 5 1 instance 6 exposed
Issued
Dec 15, 2021
Abate by
Feb 28, 2022
Penalty
Initial $9,753 · Current $8,778 Reduced
29 CFR  1910.147(c)(6)(i)(A):The periodic inspection of the energy control procedure was not performed by an authorized employee other than the one utilizing the energy control procedure being inspected:  For employees working at the Sysco building  in Palmetto Florida, a periodic inspection of the Logout/Tagout Procedures was not conducted by an authorized employee exposing employees to an amputation and electrocution hazards.
Recent events (2)
  • — I (S) $8777.7
  • — Z (S) $9753

1910.147 C06 II

Serious Gravity 5 1 instance 6 exposed
Issued
Dec 15, 2021
Abate by
Feb 28, 2022
Penalty
Initial $9,753 · Current $8,778 Reduced
29 CFR  1910.147(c)(6)(ii):The employer did not certify that the periodic inspections have been performed:  For employees working at the Sysco building  in Palmetto Florida, a periodic inspection of the Logout/Tagout Procedures for the Condenser unit removing and replacing of the drive belts on the two cooling tower fans was not certified by the employer.
Recent events (2)
  • — I (S) $8777.7
  • — Z (S) $9753

View Sysco West Coast Florida, INC.'s full OSHA safety record →

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345432090.

Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.