Safety Incidents OSHA Severe Injury Reports · 2015–2025
5,189,992Inspections Most recent open 2026-07-18 Last loaded 2026-07-22

OSHA Inspection: GREENAUER BLACKTOP INC

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of GREENAUER BLACKTOP INC in 350 FRIES ROAD, TONAWANDA, NY 14150 (NAICS 238910). OSHA activity number 345436976.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Greenauer Blacktop INC — free Get an email when a new federal OSHA severe-injury report for Greenauer Blacktop INC is published. One employer, no account, unsubscribe in one click.
Site address
350 FRIES ROAD
City
TONAWANDA
State
NY
ZIP
14150
Mailing
391 FRENCH ROAD, WEST SENECA, NY 14224
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
238910
Employees
9
Ownership type
A

2 citations on file for this inspection.

1926.152 E04

Serious Gravity 1 1 instance 1 exposed
Issued
Sep 17, 2021
Penalty
Initial $1,691 · Current $1,691
29 CFR  1926.152(e)(4):Units dispensing flammable or combustible liquids were not protected against collision damage:  a) On or about 7/23/2021, at the track area of the site, Tonawanda, NY. A 1000-gallon diesel refueling tank was located in the open area where there were construction equipment around the diesel tank. The refueling tank was not protected against collision damage.  NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (S) $1691

1926.152 G11

Other-than-serious 1 instance 1 exposed
Issued
Sep 17, 2021
Penalty
Initial $0 · Current $0
29 CFR  1926.152(g)(11):Each service or refueling area was not provided with at least one fire extinguisher having a rating of not less than 20B:C located so that an extinguisher would be within 75 feet of each pump, dispenser, underground fill pipe opening and lubrication or service center:  a) On or about 7/23/2021, at the track area of the site, Tonawanda, NY. A 1000-gallon diesel refueling tank was not provided with at least one fire extinguisher.  NO ABATEMENT CERTIFICATION REQUIRED
Recent events (1)
  • — Z (O) $0

This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345436976.