NEWTOWN, PA —
OSHA Inspection: KVK TECH, INC.
Referral inspection · Safety discipline
At a glance
On , OSHA opened a referral safety inspection of KVK TECH, INC. in 110 TERRY DRIVE AND 100 CAMPUS DRIVE, NEWTOWN, PA 18940 (NAICS 325412). OSHA activity number 345451454.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- KVK TECH, INC.
- Site address
- 110 TERRY DRIVE AND 100 CAMPUS DRIVE
- City
- NEWTOWN
- State
- PA
- ZIP
- 18940
- Mailing
- 110 TERRY DR., NEWTOWN, PA 18940
What kind of inspection was it?
- Inspection type
- Referral (C)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 325412
- Employees
- 400
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.106 D04 I
- Issued
- Feb 2, 2022
- Abate by
- Mar 31, 2022
- Penalty
- Initial $10,360 · Current $10,360
General-duty citation text
29 CFR 1910.106(d)(4)(i):Opening(s) from inside flammable and combustible storage room(s) into other rooms or buildings were not provided with noncombustible liquid-tight raised sills or ramps at least 4 inches in height: a) 110 Terry Dr., Newtown Pa, 18940, Production Area - On or about August 26, 2021, Employees were engaged in activities associated with pharmaceutical production. Flammable liquids are stored in a room, with openings into other rooms, but the room is not provided with liquid tight raised sills or ramps.
Recent events (2)
- — I (S) $10360
- — Z (S) $10360
1910.106 D04 III
- Issued
- Feb 2, 2022
- Abate by
- Mar 31, 2022
- Penalty
- Initial $8,287 · Current $8,287
General-duty citation text
29 CFR 1910.106(d)(4)(iii):Electrical wiring and equipment inside storage room(s) for Class I liquids were not of the type approved for Class I Division 2 hazardous locations: a) 110 Terry Dr., Newtown Pa, 18940, Flammable Liquid Storage Room - On or about August 26, 2021, Employees were engaged in tasks associated with pharmaceutical production. Flammable liquids are being stored in a room, but the electrical wiring is not of the type for Class I, Division II.
Recent events (2)
- — I (S) $8287
- — Z (S) $8287
1910.106 D04 IV
- Issued
- Feb 2, 2022
- Abate by
- Feb 22, 2022
- Penalty
- Initial $10,360 · Current $10,360
General-duty citation text
29 CFR 1910.106(d)(4)(iv):Each inside storage room was not provided with either a gravity or a mechanical exhaust ventilation system designed to provide for a complete change of air within the room at least six times per hour. a) 110 Terry Dr., Newtown Pa, 18940, Flammable Liquids Storage Room - On or about August 26, 2021, Employees were engaged in activities associated with pharmaceutical production. Flammable liquids are being stored in an interior room, but the room is not provided with a mechanical exhaust system capable of six air changes per hour.
Recent events (2)
- — I (S) $10360
- — Z (S) $10360
More inspections at KVK Tech, INC.
View KVK Tech, INC.'s full OSHA safety record →
More inspections in this industry (NAICS 325412)
More inspections in PA
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345451454.
Look up any company's OSHA accident reports by company, or browse severe injury reports by year, state, and company.