KINGSTON, NY —
OSHA Inspection: 21ST CENTURY MEDIA NEWSPAPER, LLC
Complaint inspection · Safety discipline
At a glance
On , OSHA opened a complaint safety inspection of 21ST CENTURY MEDIA NEWSPAPER, LLC in 115 GREEN ST, KINGSTON, NY 12401 (NAICS 511110). OSHA activity number 345453807.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- 21ST CENTURY MEDIA NEWSPAPER, LLC
- Site address
- 115 GREEN ST
- City
- KINGSTON
- State
- NY
- ZIP
- 12401
- Mailing
- 115 GREEN ST, KINGSTON, NY 12401
What kind of inspection was it?
- Inspection type
- Complaint (B)
- Scope
- Partial (B)
- Discipline
- Safety
- Advance notice
- No
- Union status
- A
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 511110
- Employees
- 18
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.36 D01
- Issued
- Jan 20, 2022
- Abate by
- Jan 26, 2022
- Penalty
- Initial $14,502 · Current $10,151 Reduced
General-duty citation text
29 CFR 1910.36(d)(1):Employee(s) were not able to open an exit route door from the inside at all times without keys, tools, or special knowledge: a) Main Entrance to Building - On or prior to July 29, 2021, exit doors for the main entrance to the building were found to be manually locked at approximately 4:30pm every night and then unlocked in the morning at approximately 8:30am every day. Employees needed a key to unlock the exit doors in order to exit the building after the exit doors were manually locked at approximately 4:30pm. b) Side Entrance to Building - On or prior to July 29, 2021, the exit door for the side entrance to the building was found to be manually locked at approximately 4:30pm every night and then unlocked in the morning at approximately 8:30am every day. Employees needed a key to unlock the exit door in order to exit the building after the exit door was manually locked at approximately 4:30pm.
Recent events (2)
- — I (O) $10151.4
- — Z (S) $14502
1910.303 B02
- Issued
- Jan 20, 2022
- Abate by
- Jan 26, 2022
- Penalty
- Initial $6,215 · Current $4,351 Reduced
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: a) Doorway Next to Copier - On or prior to July 30, 2021, relocatable power taps (RPTs) or power strips were not installed and used in accordance with instruction in the listing, labeling or certification such as, but not limited to, daisy chaining two RPTs (POWER TAP 31F8 and a ESP RPT, S/M: 420491) together that were powering a Copier (Konica Minolta, Inc., Model FK-514), a ring door bell, cell phone and water cooler. b) Editorial Room - On or prior to July 30, 2021, relocatable power taps (RPTs) or power strips were not installed and used in accordance with instruction in the listing, labeling or certification such as, but not limited to, daisy chaining RPTs together by using 3 outlet connectors to power computer equipment, televisions, and a GE portable A/C unit. c) Office Room - On or prior to July 30, 2021, relocatable power tap (RPT) or power strip was not installed and used in accordance with instruction in the listing, labeling or certification such as, but not limited to, powering a portable Black + Decker A/C unit and computer equipment.
Recent events (2)
- — I (O) $4350.5
- — Z (S) $6215
1910.37 B02
- Issued
- Jan 20, 2022
- Abate by
- Jan 26, 2022
- Penalty
- Initial $0 · Current $0
General-duty citation text
29 CFR 1910.37(b)(2):Each exit was not clearly visible and marked by a sign reading "Exit": a) Doorway next to the Copier - On or about July 30, 2021, there was no exit sign above the exit door in the office space. b) Doorway further away from Copier - On or about July 20, 2021, there was no exit sign above the exit door in the office space.