OSHA Inspection: HITCHCOCK INCORPORATED

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of HITCHCOCK INCORPORATED in 49994 E HWY 24, BURLINGTON, CO 80807 (NAICS 332999). OSHA activity number 345462790.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Hitchcock Incorporated — free Get an email when a new federal OSHA severe-injury report for Hitchcock Incorporated is published. One employer, no account, unsubscribe in one click.
Site address
49994 E HWY 24
City
BURLINGTON
State
CO
ZIP
80807
Mailing
49994 E HWY 24, BURLINGTON, CO 80807
Inspection type
Planned (H)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
332999
Employees
36
Ownership type
A

7 citations on file for this inspection.

1910.242 B

Serious Gravity 1 1 instance 1 exposed
Issued
Aug 31, 2021
Abate by
Sep 20, 2021
Penalty
Initial $3,133 · Current $1,870 Reduced
29 CFR  1910.242(b): Compressed air used for cleaning purposes was not reduced to less than 30 p.s.i.:  a) Machinist area: On or about August 3, 2021 and at times prior, a worker was exposed to hazardous air pressure at the Lagun and Summit mills where blow down devices were capable of delivering 95 p.s.i. to the discharge tip and were used for personal blow-down.
Recent events (2)
  • — I (S) $1870
  • — Z (S) $3133

1910.303 F02

Serious Gravity 5 1 instance 26 exposed
Issued
Aug 31, 2021
Abate by
Oct 4, 2021
Penalty
Initial $5,223 · Current $3,130 Reduced
29 CFR  1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident:  a) Shop:  On or about August 3, 2021 and at times prior, workers were exposed to electrical hazards from delayed power interruption while opening circuit breaker in panels MS4 and MS9 in that the function of the breaker was not identified as to its purpose.
Recent events (2)
  • — I (S) $3130
  • — Z (S) $5223

1910.305 B01 II

Serious Gravity 5 1 instance 26 exposed
Issued
Aug 31, 2021
Abate by
Oct 4, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(1)(ii):Unused openings in boxes, cabinets, or fittings were not effectively closed:  a) Behind Edelstaal drill press: On or about August 3, 2021 and at times prior, workers were exposed to electrical hazards in that a power switch box had an opening due to a missing knockout.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 B02 I

Serious Gravity 5 1 instance 26 exposed
Issued
Aug 31, 2021
Abate by
Sep 13, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(b)(2)(i): Each outlet box in completed installations did not have a cover, faceplate, or fixture canopy:  a) Break room:  On or about August 3, 2021 and at times prior, workers were exposed to electrical hazards in that an energized wall outlet was missing a faceplate.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.305 G02 III

Serious Gravity 5 1 instance 26 exposed
Issued
Aug 31, 2021
Abate by
Sep 13, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws:  a) Alzmetall Drill Press M5: a) On or about August 3, 2021 and at times prior, workers were exposed to electrical hazards in that a power cord end fitting was not providing grip to the flexible cord which allowed a direct pull to be applied to the terminal screws.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.147 C04 II D

Other-than-serious 1 instance 2 exposed
Issued
Aug 31, 2021
Abate by
Oct 4, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.147(c)(4)(ii)(D): The energy control procedures did not clearly and specifically outline the requirements for testing a machine or equipment to determine and verify the effectiveness of lockout devices, tagout devices, and other energy control measures:  a) Shop: On or about August 3, 2021 and at times prior, workers were exposed to the release of hazardous energy when following procedures that did not specify that a locked device should be tested for effectiveness to remove the hazardous energy.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

1910.1200 G01

Other-than-serious 1 instance 36 exposed
Issued
Aug 31, 2021
Abate by
Oct 19, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.1200(g)(1): Employers did not have a safety data sheet in the workplace for each hazardous chemical which they use:  a) Parts Area:  On or about August 3, 2021 and at times prior, employees were exposed to chemical hazards in that the employer did not replace outdated MSDS sheets with updated Safety Data Sheets in accordance with the Globally Harmonized System.
Recent events (2)
  • — I (O) $0
  • — Z (O) $0

View Hitchcock Incorporated's full OSHA safety record →