PECOS, TX —
OSHA Inspection: CACTUS DRILLING COMPANY LLC
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of CACTUS DRILLING COMPANY LLC in 6.2 MILES NW DIRECTION FROM PECOS MCDERMOTT STATE UNIT, PECOS, TX 79772 (NAICS 213111). OSHA activity number 345484240.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- CACTUS DRILLING COMPANY LLC
- Site address
- 6.2 MILES NW DIRECTION FROM PECOS MCDERMOTT STATE UNIT
- City
- PECOS
- State
- TX
- ZIP
- 79772
- Mailing
- 8300 SW 15TH STREET, OKLAHOMA CITY, OK 73128
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 213111
- Employees
- 847
- Ownership type
- A
Citations
3 citations on file for this inspection.
1910.304 B03 II A
- Issued
- Nov 23, 2021
- Abate by
- Dec 23, 2021
- Penalty
- Initial $7,802 · Current $4,000 Reduced
General-duty citation text
29 CFR 1910.304(b)(3)(ii)(A): All 125-volt, single-phase, 15-, 20-, and 30-ampere receptacle outlets that were not part of the permanent wiring of the building or structure and that were in use by personnel did not have ground-fault circuit-interrupter protection for personnel. On or about August 11, 2021, in the mud mixing area above the sink there was an electrical receptacle (four outlet) that was not GFCI, this condition exposed employees to electrical shock hazards .
Recent events (2)
- — I (O) $4000
- — Z (S) $7802
1910.303 B02
- Issued
- Nov 23, 2021
- Abate by
- Dec 23, 2021
- Penalty
- Initial $1,095 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(2):Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about August 11, 2021, in the Dog House, at Rig #168, employees were exposed to electrical shock hazards in the following instances. 1) A relocatable power tap was permanently secured to the wall and not used or installed in accordance with instructions included in the listing or labeling. 2) A coffee pot and microwave were plugged in directly to a APC Relocatable Power Tap and not used in accordance with instructions included in the listing or labeling .
Recent events (2)
- — I (O) $1000
- — Z (O) $1095
1910.303 B01 IV
- Issued
- Nov 23, 2021
- Penalty
- Initial $1,095 · Current $1,000 Reduced
General-duty citation text
29 CFR 1910.303(b)(1)(iv): Electric equipment was not free from recognized hazards that were likely to cause serious physical harm to employees, such as damaged electrical insulation: On or about August 11, 2021, at Rig 168, there was a 600V electrical cable that ran from the generator house to the Mud logger's trailer had outer insulation damage. This condition exposed employees electrical shock hazards.
Recent events (2)
- — I (O) $1000
- — Z (O) $1095
More inspections at Cactus Drilling Company LLC
View Cactus Drilling Company LLC's full OSHA safety record →
More inspections in this industry (NAICS 213111)
More inspections in TX
Source
This record is reproduced from the U.S. Department of Labor Open Data API (OSHA inspection dataset). The original IMIS detail view is available at OSHA's Establishment Search for activity number 345484240.