OSHA Inspection: THE DEVEREUX FOUNDATION

Planned inspection · Safety discipline

On , OSHA opened a planned safety inspection of THE DEVEREUX FOUNDATION in 390 BOOT RD, WEST CHESTER, PA 19380 (NAICS 623220). OSHA activity number 345487326.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch The Devereux Foundation — free Get an email when a new federal OSHA severe-injury report for The Devereux Foundation is published. One employer, no account, unsubscribe in one click.
Site address
390 BOOT RD
City
WEST CHESTER
State
PA
ZIP
19380
Mailing
390 BOOT RD, WEST CHESTER, PA 19380
Inspection type
Planned (H)
Scope
Complete (A)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
623220
Employees
530
Ownership type
A

4 citations on file for this inspection.

1910.28 B03 II

Serious Gravity 5 2 instances 2 exposed
Issued
Feb 10, 2022
Abate by
Mar 2, 2022
Penalty
Initial $8,287 · Current $4,972 Reduced
29 CFR  1910.28(b)(3)(ii): Each employee was not protected from tripping into or stepping into or through any hole that was less than 4 feet (1.2 m) above a lower level by covers or guardrail systems:  (a)  Bldg. 112 (Main House), Boiler Room:  A floor opening measuring approx. 19" wide by 24" deep over a sump pump pit was not covered or guarded, exposing employees to trip and fall hazards. Condition noted on or about the 6-month period of Feb. 17 - August 17, 2021.  (b) Bldg. 105 (Jackson B), Boiler Room: A floor opening measuring approx. 19" wide by 24" deep over a sump pump pit was not covered or guarded, exposing employees to trip and fall hazards. Condition noted on or about the 6-month period of Feb. 17 - August 17, 2021.
Recent events (2)
  • — I (S) $4972.2
  • — Z (S) $8287

1910.212 A01

Serious Gravity 5 1 instance 2 exposed
Issued
Feb 10, 2022
Abate by
Mar 2, 2022
Penalty
Initial $10,360 · Current $6,216 Reduced
29 CFR  1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks:  (a) Jobsite located at 390 Boot Rd, West Chester, PA: In the Mechanical Room of Bldg. 104 (Learning Center), the Trane Climate Changer Air Handler, serial no. K92C13894, did not have guards installed for a protruding rotating shaft at the sleeve bearing access point in front of the unit & a rotating belt assembly at the back of the unit, exposing employees to caught-in-between hazards.    Condition noted on or about August 17, 2021.
Recent events (2)
  • — I (S) $6216
  • — Z (S) $10360

1910.305 D02

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 10, 2022
Abate by
Mar 2, 2022
Penalty
Initial $14,502 · Current $8,701 Reduced
29 CFR  1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front.    (a) Jobsite located at 390 Boot Rd, West Chester, PA, Bldg. 102 (Greenway):  The employer did not ensure that an electrical panel was dead front, exposing maintenance employees to electric shock hazards.   Condition noted on or about August 19, 2021.
Recent events (2)
  • — I (S) $8701.2
  • — Z (S) $14502

1910.305 E01

Serious Gravity 10 1 instance 2 exposed
Issued
Feb 10, 2022
Abate by
Mar 2, 2022
Penalty
Initial $14,502 · Current $8,701 Reduced
29 CFR  1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures:    (a) Jobsite located at 390 Boot Rd, West Chester, PA:  Employees performing work inside the sprinkler room of Bldg. 104 (Learning Center) were exposed to electric shock hazards in that condensation from an overhead water pipe was dripping down and accumulating onto the electrical control panel of a Weil-McLain natural gas boiler, model no. LGB-11.   Condition noted on or about the 6-month period of Feb 17  - August 17, 2021.
Recent events (2)
  • — I (S) $8701.2
  • — Z (S) $14502

View The Devereux Foundation's full OSHA safety record →