WEST CHESTER, PA —
OSHA Inspection: THE DEVEREUX FOUNDATION
Planned inspection · Safety discipline
At a glance
On , OSHA opened a planned safety inspection of THE DEVEREUX FOUNDATION in 390 BOOT RD, WEST CHESTER, PA 19380 (NAICS 623220). OSHA activity number 345487326.
OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.
Where did this inspection happen?
- Establishment
- THE DEVEREUX FOUNDATION
- Site address
- 390 BOOT RD
- City
- WEST CHESTER
- State
- PA
- ZIP
- 19380
- Mailing
- 390 BOOT RD, WEST CHESTER, PA 19380
What kind of inspection was it?
- Inspection type
- Planned (H)
- Scope
- Complete (A)
- Discipline
- Safety
- Advance notice
- No
- Union status
- B
When did the case open and close?
- Opened
- Closing conference
- Case closed
- Last modified
- Data loaded
Establishment context
- NAICS code
- 623220
- Employees
- 530
- Ownership type
- A
Citations
4 citations on file for this inspection.
1910.28 B03 II
- Issued
- Feb 10, 2022
- Abate by
- Mar 2, 2022
- Penalty
- Initial $8,287 · Current $4,972 Reduced
General-duty citation text
29 CFR 1910.28(b)(3)(ii): Each employee was not protected from tripping into or stepping into or through any hole that was less than 4 feet (1.2 m) above a lower level by covers or guardrail systems: (a) Bldg. 112 (Main House), Boiler Room: A floor opening measuring approx. 19" wide by 24" deep over a sump pump pit was not covered or guarded, exposing employees to trip and fall hazards. Condition noted on or about the 6-month period of Feb. 17 - August 17, 2021. (b) Bldg. 105 (Jackson B), Boiler Room: A floor opening measuring approx. 19" wide by 24" deep over a sump pump pit was not covered or guarded, exposing employees to trip and fall hazards. Condition noted on or about the 6-month period of Feb. 17 - August 17, 2021.
Recent events (2)
- — I (S) $4972.2
- — Z (S) $8287
1910.212 A01
- Issued
- Feb 10, 2022
- Abate by
- Mar 2, 2022
- Penalty
- Initial $10,360 · Current $6,216 Reduced
General-duty citation text
29 CFR 1910.212(a)(1): One or more methods of machine guarding was not provided to protect the operator and other employees in the machine area from hazards such as those created by point of operation, ingoing nip points, rotating parts, flying chips and sparks: (a) Jobsite located at 390 Boot Rd, West Chester, PA: In the Mechanical Room of Bldg. 104 (Learning Center), the Trane Climate Changer Air Handler, serial no. K92C13894, did not have guards installed for a protruding rotating shaft at the sleeve bearing access point in front of the unit & a rotating belt assembly at the back of the unit, exposing employees to caught-in-between hazards. Condition noted on or about August 17, 2021.
Recent events (2)
- — I (S) $6216
- — Z (S) $10360
1910.305 D02
- Issued
- Feb 10, 2022
- Abate by
- Mar 2, 2022
- Penalty
- Initial $14,502 · Current $8,701 Reduced
General-duty citation text
29 CFR 1910.305(d)(2): Panelboards were not mounted in cabinets, cutout boxes, or enclosures designed for the purpose and shall be dead front. (a) Jobsite located at 390 Boot Rd, West Chester, PA, Bldg. 102 (Greenway): The employer did not ensure that an electrical panel was dead front, exposing maintenance employees to electric shock hazards. Condition noted on or about August 19, 2021.
Recent events (2)
- — I (S) $8701.2
- — Z (S) $14502
1910.305 E01
- Issued
- Feb 10, 2022
- Abate by
- Mar 2, 2022
- Penalty
- Initial $14,502 · Current $8,701 Reduced
General-duty citation text
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: (a) Jobsite located at 390 Boot Rd, West Chester, PA: Employees performing work inside the sprinkler room of Bldg. 104 (Learning Center) were exposed to electric shock hazards in that condensation from an overhead water pipe was dripping down and accumulating onto the electrical control panel of a Weil-McLain natural gas boiler, model no. LGB-11. Condition noted on or about the 6-month period of Feb 17 - August 17, 2021.
Recent events (2)
- — I (S) $8701.2
- — Z (S) $14502
More inspections at The Devereux Foundation
View The Devereux Foundation's full OSHA safety record →