OSHA Inspection: OLON RICERCA BIOSCIENCE, LLC

Referral inspection · Safety discipline

On , OSHA opened a referral safety inspection of OLON RICERCA BIOSCIENCE, LLC in 7528 AUBURN ROAD, PAINESVILLE, OH 44077 (NAICS 541715). OSHA activity number 345497481.

What this inspection record means

OSHA opens inspections for many reasons — routine scheduling under a national or local emphasis program, an employee complaint or referral, or a follow-up after a reported injury. Opening or conducting an inspection is not itself an allegation or a finding that this employer broke any rule; any findings appear as the citations listed below, and citations can be contested, reduced, or withdrawn.

Watch Olon Ricerca Bioscience, LLC — free Get an email when a new federal OSHA severe-injury report for Olon Ricerca Bioscience, LLC is published. One employer, no account, unsubscribe in one click.
Site address
7528 AUBURN ROAD
City
PAINESVILLE
State
OH
ZIP
44077
Mailing
7528 AUBURN ROAD, PAINESVILLE, OH 44077
Inspection type
Referral (C)
Scope
Partial (B)
Discipline
Safety
Advance notice
No
Union status
B
Opened
Closing conference
Case closed
Last modified
Data loaded
NAICS code
541715
Employees
194
Ownership type
A

8 citations on file for this inspection.

1910.147 C06 I C

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 15, 2021
Abate by
Jan 3, 2022
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.147(c)(6)(i)(C): Where lockout was used for energy control, the periodic inspection did not include a review, between the inspector and each authorized employee, of that employee's responsibilities under the energy control procedure being inspected:   On or about August 23, 2021, the employer failed to conduct the periodic inspection with each authorized employee on the responsibilities under the specific procedure for all energy control work. The employer did not provide any recent periodic inspection records.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778

1910.303 E01 II

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 15, 2021
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.303(e)(1)(ii): Electrical equipment was used when the markings giving voltage, current, wattage, or other ratings as necessary were missing:  On or about August 23, 2021, the employer did not ensure electrical equipment was marked with the voltage, current, wattage, and other ratings, thereby exposing employees to an electrical hazard while working on an metal enclosed electrical cabinet located in the US 4 Substation. The employee was attempting to determine the cause of an electrical outage at the facility building "B" and was testing fuses.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778

1910.303 H05 III A

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 15, 2021
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.303(h)(5)(iii)(A): All entrances were not kept locked unless they were under the observation of a qualified person at all times:  On or about August 23, 2021, the employer did not ensure all entrances to high voltage electrical rooms over 600 volts were locked and only accessible to qualified employees, in that, the entrance to the high voltage electrical room containing three phase primary voltage (4KV), located in Building B, US 4 Penthouse substation, was not marked and the room was not secured, exposing employees to an electrical hazard while storing material in the room. Unauthorized employees were allowed to access the room and the room was used for overflow storage including filters and other cleaning supplies.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778

1910.303 H05 III B

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 15, 2021
Penalty
Initial $0 · Current $0
29 CFR  1910.303(h)(5)(iii)(B): Permanent and conspicuous warning signs were not provided, reading substantially as follows: "DANGER--HIGH VOLTAGE--KEEP OUT":  On or about August 23, 2021, the employer did not ensure all entrances to high voltage rooms containing electrical equipment over 600 volts were marked with appropriate signs.  The entrance to the high voltage electrical room containing three phase primary voltage (4KV), located in Building B, US 4 Penthouse substation, was not marked with proper signage, exposing employees to an electrical hazard while storing material in the room.
Recent events (2)
  • — I (S) $0
  • — Z (S) $0

1910.332 B03

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 15, 2021
Abate by
Jan 3, 2022
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.332(b)(3): Qualified persons (i.e. those permitted to work on or near exposed energized parts) were not, at a minimum, trained in and familiar with the following: (i) The skills and techniques necessary to distinguish exposed live parts from other parts of electric equipment, (ii) The skills and techniques necessary to determine the nominal voltage of exposed live parts, and (iii) The clearance distances specified in 1910.333(c) and the corresponding voltages to which the qualified person will be exposed.   On or about August 23, 2021, the employer did not ensure employees were adequately trained in the safety-related work practices to be employed to prevent electric shock or other injuries resulting from either direct or indirect electrical contacts, when work is performed near or on equipment or circuits which are or may be energized. Specifically employees were not trained in electrical work for voltages greater than 600 volts.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778

1910.333 A02

Serious Gravity 5 1 instance 2 exposed
Issued
Nov 15, 2021
Abate by
Jan 3, 2022
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.333(a)(2): Where exposed live parts were not deenergized (i.e., for reasons of increased or additional hazards or infeasibility), other safety-related work practices were not used to protect employees who could be exposed to the electrical hazards involved:  On or about August 23, 2021, the employer did not ensure employees working on electrical equipment with exposed live parts employed safety related work practices to protect against exposure to electrical shock and arc flash hazards.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778

1910.334 C03

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 15, 2021
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.334(c)(3): Rating of equipment. Test instruments and equipment and their accessories were not rated for the circuits and equipment to which they were connected and were not designed for the environment they were used.   On or about August 23, 2021, the employer did not ensure employees working with test equipment used the proper rated equipment for the voltage being tested.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778

1910.335 A01 I

Serious Gravity 5 1 instance 1 exposed
Issued
Nov 15, 2021
Penalty
Initial $8,778 · Current $5,705 Reduced
29 CFR  1910.335(a)(1)(i): Employees working in areas where there were potential electrical hazards were not provided with electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed:   On or about August 23, 2021, the employer did not ensure employees working with test equipment used the proper rated equipment for the voltage being tested. The employer allowed employees to use a 1000 voltmeter to test primary voltages over 4000 volts.
Recent events (2)
  • — I (S) $5705
  • — Z (S) $8778